Plan Review Notes
Plan Review Notes For Permit 17041276
Permit Number 17041276
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-02 15:06:111ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041276
 5/2/17
  
 1) THE MECHANICAL PLANS ARE INCOMPLETE. PLEASE PROVIDE
 THE FOLLOWING:
  
 A) AC COOLING HEATING CALCULATIONS- SECTION C403.2.1
 FBC-14 ENERGY CONSERVATION.
 B) ENERGY CALCULATIONS- SECTIONS C101.3, C101.5, AND
 C401.2 FBC-14 ENERGY CONSERVATION.
 C) MINIMUM VENTIALTION CALCULATIONS FOR ALL OCCUPIED
 ROOMS AND SPACES. PROVIDE A TABLE THAT INCLUDES THE
 REQUIRED AND PROVIDED CFMS OF OUTSIDE AIR- TABLE 403.3
 FBC-14 MECHANICAL.
 D) EXHAUST VENTILATION CALCULATIONS FOR THE RESTROOMS-
 TABLE 403.3
 E) COMBUSTION AIR CALCULATIONS AND VENTING PLANS FOR
 THE GAS DRYERS - SECTION 304 AND 501.1 FBC-14 ENERGY
 CONSERVATION.
 F) COMPLETE DUCT LAYOUT AND AIR DISTRIBUTION PLANS
 SHOWING DUCT SIZES, DIFFUSER AND RETURN GRILL SIZES,
 TRANSFER GRILLS OR DUCTS WHERE REQUIRED, AND CFM'S AT
 EACH DEVICE.
 G) COMPLETE AC EQUIPMENT SCHEDULES THAT INDICATE THE
 MAKES AND MODELS OF THE COMPONENTS, COOLING AND HEATING
 CAPACITIES, SUPPLY CFMS, EFFICIENCY RATINGS, AND
 ELECTRICAL DATA.
 H) WIND LOAD ENGINEERING FOR INSTALLATION OF THE
 EXTERIOR CONDENSERS.
  
 2) SHEET A-14: THE PLAN APPEARS TO SHOW AN AIR HANDLER
 IN THE ATTIC ABOVE THE GREAT ROOM WHICH IS PROHIBITED
 PER SECTION C403.2.7.6 FBC-14 ENERGY COMPLIANCE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER