| Notes |
| Date |
Text |
| 2017-05-18 10:10:20 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. THE FIRST SECTION OF PE PIPE SHALL BE 1 1/4" PER FBC | | | FUEL GAS TABLE 402.4(22) USING LONGEST LENGTH METHOD @ | | | 265'-8" WHICH WOULD BE ROUNDED TO 300' ON THE TABLE. | | | | | | 2. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE | | | FBC-2014 FUEL GAS CODE SEC. 304. | | | | | | 3. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND | | | TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE | | | SEC. 502 THRU 505. | | | | | | 4. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL | | | GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA | | | 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2 | | | | | | | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|