| 2017-05-04 14:59:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET A 1 - THERE ARE REFERENCES TO ANY CURRENT |
| | EDITIONS OF THE NFPA 1 & 101. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | 2) A LIFE SAFETY REVIEW SHEET WAS NOT PROVIDED |
| | INDICATING COMPLIANCE WITH ANY LIFE SAFETY OCCUPANCY |
| | CHAPTER OF NFPA 101. IT APPEARS THAT THE OCCUPANCY MAY |
| | BE CHAPTER IS NFPA 101, CHAPTER 30, NEW APARTMENT |
| | BUILDINGS. CHAPTER 32 RESIDENTIAL BOARD AND CARE, OR |
| | CHAPTER 26 LODGING AND ROOMING HOUSES. |
| | |
| | IT APPEARS THAT THERE ARE TWO SEPARATE SLEEPING AREAS |
| | PER BEDROOM. |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS AS TO THE USE AND |
| | FUNCTION OF THESE APARTMENTS AND THE APPLICABLE NFPA |
| | 101 OCCUPANCY CHAPTER AND ALL LIFE SAFETY FEATURES |
| | REQUIREMENTS OF THAT CHAPTER. |
| | |
| | |
| | |
| | 3) SHEET A 3 - THE IS AN AREA INDICATED AS CASUAL |
| | ROOM/GUEST ROOM THAT APPEARS TO BE AN ASSEMBLY |
| | SPACE/OCCUPANCY. |
| | |
| | THERE IS NO INDICATION OF COMPLAINCE WITH THE ASSEMBLY |
| | OCCPANCY CODE. |
| | |
| | PLEASE REVIEW AND COORECT ENSURE COMPLIANCE WITH ALL |
| | APPLICABLE NFPA 101 REQUIREMENTS. |
| | |
| | |
| | |
| | 4) SHEET A 3 - A DOOR/GATE, # 11, IS INDICATED IN THE |
| | PATH OF EXIT TRAVEL. BUT NO DETAIL PROVIDED AS TO THE |
| | EXIT HARDWARE IN COMPLINACE WITH NFPA 101, CHAPTER 7, |
| | MEANS OF EGRESS. |
| | |
| | 30.2.2.2 DOORS. |
| | 30.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 30.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH |
| | 30.2.2.2.2.1, 30.2.2.2.2.2, 30.2.2.2.2.3, OR |
| | 30.2.2.2.2.4. |
| | 30.2.2.2.2.1* NO DOOR IN ANY MEANS OF EGRESS SHALL BE |
| | LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED. |
| | |
| | 7.2.1.4 SWING AND FORCE TO OPEN. |
| | 7.2.1.4.1* SWINGING-TYPE DOOR ASSEMBLY REQUIREMENT. ANY |
| | DOOR ASSEMBLY IN A MEANS OF EGRESS SHALL BE OF THE |
| | SIDE-HINGED OR PIVOTED-SWINGING TYPE, AND SHALL BE |
| | INSTALLED TO BE CAPABLE OF SWINGING FROM ANYPOSITION TO |
| | THE FULL REQUIRED WIDTH OF THE OPENING IN WHICH IT IS |
| | INSTALLED, UNLESS OTHERWISE SPECIFIED AS FOLLOWS: |
| | (1) DOOR ASSEMBLIES IN DWELLING UNITS, AS PROVIDED IN |
| | CHAPTER 24, SHALL BE PERMITTED. |
| | (2) DOOR ASSEMBLIES IN RESIDENTIAL BOARD AND CARE |
| | OCCUPANCIES, AS PROVIDED IN CHAPTERS 32 AND 33, SHALL |
| | BE PERMITTED. |
| | (3) WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, |
| | HORIZONTAL-SLIDING OR VERTICAL-ROLLING SECURITY GRILLES |
| | OR DOOR ASSEMBLIES THAT ARE PART OF THE REQUIRED MEANS |
| | OF EGRESS SHALL BE PERMITTED, PROVIDED THAT ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (A) SUCH GRILLES OR DOOR ASSEMBLIES SHALL REMAIN |
| | SECURED IN THE FULLY OPEN POSITION DURING THE PERIOD OF |
| | OCCUPANCY BY THE GENERAL PUBLIC. |
| | (B) ON OR ADJACENT TO THE GRILLE OR DOOR OPENING, THERE |
| | SHALL BE A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT |
| | LESS THAN 1 IN. (25 MM) HIGH ON A CONTRASTING |
| | BACKGROUND THAT READS AS FOLLOWS: THIS DOOR TO REMAIN |
| | OPEN WHEN THE BUILDING IS OCCUPIED. |
| | (C) DOOR LEAVES OR GRILLES SHALL NOT BE BROUGHT TO THE |
| | CLOSED POSITION WHEN THE SPACE IS OCCUPIED. |
| | (D) DOOR LEAVES OR GRILLES SHALL BE OPERABLE FROM |
| | WITHIN THE SPACE WITHOUT THE USE OF ANY SPECIAL |
| | KNOWLEDGE OR EFFORT. |
| | (E) WHERE TWO OR MORE MEANS OF EGRESS ARE REQUIRED, NOT |
| | MORE THAN HALF OF THE MEANS OF EGRESS SHALL BE EQUIPPED |
| | WITH HORIZONTAL-SLIDING OR VERTICAL-ROLLING GRILLES OR |
| | DOOR ASSEMBLIES. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| | OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER |
| | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE |
| | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | |
| | |
| | PLEASE PROVIDE DETAILS MEETING THE REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 5) SHEET A 3 & 5 - STAIRS, HARDRAILS AND RAILINGS ARE |
| | INDICATED; HOWEVER NO DETAILS ARE PROVIDED. |
| | |
| | PER NFPA 101, CHAPTER 7, MEANS OF EGRESS |
| | |
| | 7.2.2 STAIRS. |
| | 7.2.2.1 GENERAL. |
| | 7.2.2.1.1 STAIRS USED AS A COMPONENT IN THE MEANS OF |
| | EGRESS SHALL CONFORM TO THE GENERAL REQUIREMENTS OF |
| | SECTION 7.1 AND TO THE SPECIAL REQUIREMENTS OF 7.2.2, |
| | UNLESS OTHERWISE SPECIFIED IN 7.2.2.1.2. |
| | |
| | 7.2.2.3 STAIR DETAILS. |
| | 7.2.2.3.1 CONSTRUCTION. |
| | 7.2.2.3.1.1 ALL STAIRS SERVING AS REQUIRED MEANS OF |
| | EGRESS SHALL BE OF PERMANENT FIXED CONSTRUCTION, UNLESS |
| | THEY ARE STAIRS SERVING SEATING THAT IS DESIGNED TO BE |
| | REPOSITIONED IN ACCORDANCE WITH CHAPTERS 12 AND 13. |
| | |
| | 7.2.2.4 GUARDS AND HANDRAILS. |
| | 7.2.2.4.1 HANDRAILS. |
| | 7.2.2.4.1.1 STAIRS AND RAMPS SHALL HAVE HANDRAILS ON |
| | BOTH SIDES, UNLESS OTHERWISE PERMITTED IN 7.2.2.4.1.5 |
| | OR 7.2.2.4.1.6. |
| | |
| | PLEASE PROVIDE DETAILS MEETING THE REQUIREMENTS |
| | |
| | |
| | |
| | 6) SEET A 6 & 7 - THERE ARE NO EXIT SIGNS IN ANY EXIT |
| | CORRIDOR OR ASSEMBLY AREAS. |
| | |
| | NFPA 101 |
| | |
| | ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS SHALL |
| | BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | |
| | MARKING OF MEANS OF EGRESS. MEANS OF EGRESS SHALL HAVE |
| | SIGNS IN ACCORDANCE WITH SECTION 7.10 IN ALL BUILDINGS |
| | REQUIRING MORE THAN ONE EXIT. |
| | |
| | |
| | |
| | |
| | 7) ANY SHEETS - THE SUBMITTAL DOES NOT INDICATED EXITS |
| | LEADING TO A PUBLIC WAY. |
| | |
| | DISCHARGE FROM EXITS. EXIT DISCHARGE SHALL COMPLY WITH |
| | SECTION 7.7. |
| | |
| | 7.7 DISCHARGE FROM EXITS. |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT |
| | DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH |
| | 7.7.1.4. |
| | |
| | PLEASE PROVIDE A DETAIL INDICATING COMPLIANCE WITH THE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 8) NO SHEET SUBMITTALS - THERE ARE NO FIRE SPRINKLER |
| | DOCUMENTS WITH THIS SUBMITTAL. |
| | |
| | 30.3.5 EXTINGUISHMENT REQUIREMENTS. |
| | 30.3.5.1 ALL BUILDINGS SHALL BE PROTECTED THROUGHOUT BY |
| | AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | INSTALLED IN ACCORDANCE WITH 30.3.5.2. |
| | |
| | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, |
| | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | 61G15-32.003 COMMON REQUIREMENTS TO ALL FIRE PROTECTION |
| | ENGINEERING |
| | DOCUMENTS. |
| | (1) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL PROVIDE THE ENGINEERING REQUIREMENTS TO BE USED |
| | IN THE PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS AND TO INDICATE THE NATURE AND SCOPE OF THE |
| | WORK, AND TO DESCRIBE, DETAIL, DIMENSION, LABEL AND |
| | DEFINE THE FIRE PROTECTION COMPONENTS, SYSTEM(S), |
| | MATERIALS, ASSEMBLIES, EQUIPMENT AND ITS STRUCTURAL AND |
| | UTILITY SUPPORT SYSTEM(S), INSOFAR AS THEY INVOLVE THE |
| | SAFEGUARDING OF LIFE, HEALTH OR PROPERTY. |
| | (2) THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS |
| | SHALL SPECIFY THE APPLICABLE REQUIREMENTS FOR THE |
| | ACCEPTANCE TESTING OF THE FIRE PROTECTION SYSTEM AND |
| | COMPONENTS, WHICH SHALL BE BASED UPON APPLICABLE CODES |
| | AND STANDARDS, WHERE AVAILABLE. |
| | (3) THE OCCUPANCY OF THE AREA OR DESCRIPTION OF A |
| | SPECIFIC HAZARD BEING PROTECTED BY THE FIRE PROTECTION |
| | SYSTEM(S) SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (4) THE APPLICABLE CODE AND STANDARD TO BE USED IN THE |
| | PREPARATION OF THE FIRE PROTECTION SYSTEM LAYOUT |
| | DOCUMENTS SHALL BE SHOWN ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. WHEN CODES AND STANDARDS ARE NOT |
| | AVAILABLE OR APPLICABLE, AND SAID LAYOUT DOCUMENTS ARE |
| | TO BE BASED ON ENGINEERING JUDGMENT, ANY REASONS AND |
| | ASSUMPTIONS MADE TO DEVELOP THE FIRE PROTECTION CONCEPT |
| | SHALL BE IDENTIFIED ON THE FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENTS. |
| | (5) STRUCTURAL SUPPORT AND STRUCTURAL OPENINGS REQUIRED |
| | BY THE FIRE PROTECTION SYSTEM SHALL BE SHOWN ON THE |
| | FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS AND SHALL |
| | BE REFERENCED ON STRUCTURAL ENGINEERING DOCUMENTS. |
| | (6) WHEN LAYOUT DOCUMENTS CONTAIN MATERIAL DEVIATION |
| | FROM THE ENGINEER OF RECORD'S FIRE PROTECTION SYSTEM |
| | ENGINEERING DOCUMENT, SUCH LAYOUT DOCUMENTS ARE NOT |
| | COMPLIANT UNLESS THEY ARE ACCOMPANIED BY REVISED |
| | ENGINEERING DOCUMENTS MADE AND SEALED BY THE ENGINEER |
| | OF RECORD FOR THE FIRE PROTECTION SYSTEM. |
| | (7) REQUIREMENTS FOR ACTIVATION CONTROL SYSTEMS, |
| | SEQUENCE, OPERATING PARAMETERS, INTERLOCKS, SAFETY |
| | RELATED DEVICES, INDICATORS AND ALARMS, SHALL BE SHOWN |
| | ON THE FIRE PROTECTION SYSTEM ENGINEERING DOCUMENTS, |
| | UNLESS SHOWN ON OTHER RELATED DOCUMENTS. |
| | (8) ANY INFORMATION DEEMED APPROPRIATE BY THE ENGINEER |
| | OF RECORD TO ASSIST THE AUTHORITY HAVING JURISDICTION |
| | IN UNDERSTANDING THE OWNER?S INTENDED USE AND PROPOSED |
| | PROTECTION OF THE BUILDING OR FACILITY AND TO PROVIDE |
| | SUFFICIENT DIRECTION TO THE INSTALLATION CONTRACTOR OR |
| | OTHER INTERESTED PARTIES REGARDING THE LAYOUT OF THE |
| | SYSTEM(S), SHALL BE INCLUDED IN THE FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.003, AMENDED |
| | 4-2-2000, 6-26-01 |
| | |
| | 61G15-32.004 DESIGN OF WATER BASED FIRE PROTECTION |
| | SYSTEMS. |
| | (1) WATER BASED FIRE PROTECTION SYSTEMS INCLUDE, BUT |
| | ARE NOT LIMITED TO, AUTOMATIC SPRINKLER SYSTEMS OF WET, |
| | DRY, FINE WATER SPRAY (MIST), MANUAL, AND DELUGE VALVE |
| | CONTROLLED TYPES, PUMPING SYSTEMS, STANDPIPES, FIRE |
| | WATER MAINS AND DEDICATED FIRE PROTECTION WATER |
| | SOURCES. |
| | (2) TO ENSURE MINIMUM DESIGN QUALITY IN FIRE PROTECTION |
| | SYSTEM ENGINEERING DOCUMENTS, SAID DOCUMENTS SHALL |
| | INCLUDE AS A MINIMUM THE FOLLOWING INFORMATION WHEN |
| | APPLICABLE: |
| | (A) THE POINT OF SERVICE FOR THE FIRE PROTECTION WATER |
| | SUPPLY AS DEFINED BY 633.021(18) F.S. |
| | (B) APPLICABLE NFPA STANDARD TO BE APPLIED, OR IN THE |
| | CASE WHERE NO SUCH STANDARD EXISTS, THE ENGINEERING |
| | STUDY, JUDGMENTS, AND/OR PERFORMANCE BASED ANALYSIS AND |
| | CONCLUSIONS. |
| | (C) CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA. |
| | (D) DESIGN APPROACH, WHICH INCLUDES SYSTEM TYPE, |
| | DENSITIES, DEVICE TEMPERATURE RATING, AND SPACING FOR |
| | EACH SEPARATE 42 HAZARD OCCUPANCY. |
| | (E) CHARACTERISTICS OF WATER SUPPLY TO BE USED, SUCH AS |
| | MAIN SIZE AND LOCATION, WHETHER IT IS DEAD-END OR |
| | CIRCULATING; AND IF DEAD-END, THE DISTANCE TO THE |
| | NEAREST CIRCULATING MAIN, AS WELL AS ITS MINIMUM |
| | DURATION AND RELIABILITY FOR THE MOST HYDRAULICALLY |
| | DEMANDING DESIGN AREA. |
| | (F) WHEN PRIVATE OR PUBLIC WATER SUPPLIES ARE USED, THE |
| | FLOW TEST DATA, INCLUDING DATE AND TIME OF TEST, WHO |
| | CONDUCTED TEST OR SUPPLIED INFORMATION, TEST ELEVATION, |
| | STATIC GAUGE PRESSURE AT NO FLOW, FLOW RATE WITH |
| | RESIDUAL GAUGE PRESSURE, HYDRANT BUTT COEFFICIENT, AND |
| | LOCATION OF TEST IN RELATION TO THE HYDRAULIC POINT OF |
| | SERVICE. |
| | (G) VALVING AND ALARM REQUIREMENTS TO MINIMIZE |
| | POTENTIAL FOR IMPAIRMENTS AND UNRECOGNIZED FLOW OF |
| | WATER. |
| | (H) MICROBIAL INDUCED CORROSION (MIC). THE ENGINEER OF |
| | RECORD SHALL MAKE REASONABLE EFFORTS TO IDENTIFY WATER |
| | SUPPLIES THAT COULD LEAD TO MICROBIAL INDUCED CORROSION |
| | (MIC). SUCH EFFORTS MAY CONSIST OF DISCUSSIONS WITH THE |
| | LOCAL WATER PURVEYOR AND/OR FIRE OFFICIAL, FAMILIARITY |
| | WITH CONDITIONS IN THE LOCAL AREA, OR LABORATORY |
| | TESTING OF WATER SUPPLIES. WHEN CONDITIONS ARE FOUND |
| | THAT MAY RESULT IN MIC CONTAMINATION OF THE FIRE |
| | PROTECTION PIPING, THE ENGINEER SHALL DESIGN CORRECTIVE |
| | MEASURES. |
| | (I) BACKFLOW PREVENTION AND METERING SPECIFICATIONS AND |
| | DETAILS TO MEET LOCAL WATER PURVEYOR REQUIREMENTS |
| | INCLUDING MAXIMUM ALLOWABLE PRESSURE DROP. |
| | (J) QUALITY AND PERFORMANCE SPECIFICATIONS OF ALL YARD |
| | AND INTERIOR FIRE PROTECTION COMPONENTS. |
| | (3) CONTRACTOR SUBMITTALS WHICH DEVIATE FROM THE ABOVE |
| | MINIMUM DESIGN PARAMETERS SHALL BE CONSIDERED MATERIAL |
| | DEVIATIONS AND REQUIRE SUPPLEMENTAL ENGINEERING |
| | APPROVAL AND DOCUMENTATION. |
| | (4) IN THE EVENT THE ENGINEER OF RECORD PROVIDES MORE |
| | INFORMATION AND DIRECTION THAN IS ESTABLISHED ABOVE, HE |
| | OR SHE SHALL BE HELD RESPONSIBLE FOR THE TECHNICAL |
| | ACCURACY OF THE WORK IN ACCORDANCE WITH APPLICABLE |
| | CODES, STANDARDS, AND SOUND ENGINEERING PRINCIPLES. |
| | SPECIFIC AUTHORITY 471.008, 471.033(2), FS |
| | LAW IMPLEMENTED 471.005(7), 471.033(2), FS |
| | HISTORY?NEW 5-19-93, FORMERLY 21H-32.004, AMENDED |
| | 4-2-2000, 6-26-01, 7-12-05 |
| | |
| | |
| | PLEASE REVIEW AND PROVIDES APPLICABLE SIGNED AND SEALED |
| | EOR PLAN SHEETS OR WRITTEN NARRATIVE DOCUMENT |
| | CONTAINING THE SAME INFO. SHOP DRAWINGS CAN THEN BE |
| | PRODUCED, PREPARED AND SUBITTED SEPARATELY BY A FIRE |
| | SPRINKLER CONTRACTOR. |
| | |
| | |
| | |
| | 9) SHEET A 8 & 9 - LIGHTWEIGHT TRUSS FLOORS AND TRUSSES |
| | ARE INDICATED. |
| | |
| | PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED FOR |
| | STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE CONSTRUCTION. |
| | ANY COMMERCIAL, INDUSTRIAL, OR ANY MULTIUNIT |
| | RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE WHICH USES |
| | HORIZONTAL OR VERTICAL LIGHT-FRAME TRUSS-TYPE |
| | CONSTRUCTION IN ANY PORTION SHALL BE MARKED WITH A |
| | MALTESE CROSS SIGN MEASURING 8 INCHES HORIZONTALLY AND |
| | 8 INCHES VERTICALLY, OF A BRIGHT RED REFLECTIVE COLOR. |
| | THE APPROVED SYMBOL SHALL BE PLACED WITHIN 24 INCHES TO |
| | THE LEFT OF THE MAIN ENTRY DOOR. |
| | 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE |
| | MARKED WITH THE LETTER "R". |
| | 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS |
| | SHALL BE MARKED WITH THE LETTER "F". |
| | 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF |
| | SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F". |
| | |
| | |
| | |
| | 10) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 11) THERE IS INSUFFICIENT INFORMATION SUBMITTED TO DO A |
| | COMPLETE REVIEW OF THE LIFE SAFETY FEATURES AND |
| | PROTECTION OF THIS PROJECT. |
| | |
| | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| | OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |