| Plan Review Notes For Permit 17041265 |
| Permit Number |
17041265 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-06-22 07:18:48 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041265 | | | 6/22/17 | | | | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) PROVIDE MECHANICAL DEMOLTION AND ALTERATION PLANS. | | | IT APPEARS THAT THE REMOVAL OF THE ROOM PATRTITIONS TO | | | ENLARGE THE BREAK AND CONFERENCE ROOMS WILL RESULT IN | | | CHANGES TO THE AIR DISTRIBUTION COMPONENTS. PLEASE SHOW | | | THOSE CHANGES ON THE PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|