2017-06-22 07:18:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041265
 6/22/17
  
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) PROVIDE MECHANICAL DEMOLTION AND ALTERATION PLANS.
 IT APPEARS THAT THE REMOVAL OF THE ROOM PATRTITIONS TO
 ENLARGE THE BREAK AND CONFERENCE ROOMS WILL RESULT IN
 CHANGES TO THE AIR DISTRIBUTION COMPONENTS. PLEASE SHOW
 THOSE CHANGES ON THE PLAN.
  