| Plan Review Notes For Permit 17041265 |
| Permit Number |
17041265 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-11 15:50:41 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | | | | NEED THE FOLLOWING INFORMATION PRIOR TO FINAL | | | ELECTRICAL INSPECTION. | | | | | | C405.5 INTERIOR LIGHTING POWER REQUIREMENTS | | | (PRESCRIPTIVE). | | | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL | | | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION | | | C405.5.1 | | | IS NO GREATER THAN THE INTERIOR LIGHTING POWER | | | CALCULATED UNDER SECTION C405.5.2. | | | | | | C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER. | | | THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS) | | | SHALL BE THE SUM OF THE WATTS OF ALL INTERIOR LIGHTING | | | EQUIPMENT | | | AS DETERMINED IN ACCORDANCE WITH SECTIONS C405.5.1.1 | | | THROUGH C405.5.1.4. | | | | | | C405.2 LIGHTING CONTROLS (MANDATORY). | | | LIGHTING SYSTEMS SHALL BE PROVIDED WITH CONTROLS AS | | | SPECIFIED IN SECTIONS C405.2.1, C405.2.2, C405.2.3 AND | | | C405.2.4 |
|