| Notes |
| Date |
Text |
| 2017-05-03 09:09:30 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041264 | | | 5/2/17 | | | | | | 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING | | | BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES INVOLVED IN THE | | | ALTERATION- SEE TABLE 403.3 FBC-14 MECHANICAL. PROVIDE | | | A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED | | | CFMS OF OUTDOOR AIR. | | | | | | 2) SHOW COMPLIANCE WITH C403.2.7.5 FBC-14 ENERGY | | | CONSERVATION CODE FOR AIR DISTRIBUTION, AND DUCT SYSTEM | | | SIZING. | | | | | | 3) SUBMIT A MECHANICAL SUB-PERMIT APPLICATION FOR | | | ALTMAN BROTHERS, OR PROVIDE A SHOP DRAWING STAMP ON THE | | | PLANS FROM THE ARCHITECT OF RECORD- PLEASE SEE SECTION | | | 105.3.1.2 WPB AMENDMENTS TO THE FBC. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|