Plan Review Notes
Plan Review Notes For Permit 17041264
Permit Number 17041264
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-03 09:09:301ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041264
 5/2/17
  
 1) REFER TO SECTIONS 809.1 & 809.2 FBC-14 EXISTING
 BUILDING CODE AND PROVIDE MINIMUM VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES INVOLVED IN THE
 ALTERATION- SEE TABLE 403.3 FBC-14 MECHANICAL. PROVIDE
 A SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDED
 CFMS OF OUTDOOR AIR.
  
 2) SHOW COMPLIANCE WITH C403.2.7.5 FBC-14 ENERGY
 CONSERVATION CODE FOR AIR DISTRIBUTION, AND DUCT SYSTEM
 SIZING.
  
 3) SUBMIT A MECHANICAL SUB-PERMIT APPLICATION FOR
 ALTMAN BROTHERS, OR PROVIDE A SHOP DRAWING STAMP ON THE
 PLANS FROM THE ARCHITECT OF RECORD- PLEASE SEE SECTION
 105.3.1.2 WPB AMENDMENTS TO THE FBC.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  