| Plan Review Notes For Permit 17041264 |
| Permit Number |
17041264 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-30 14:55:38 | 1. PROVIDE ELECTRICAL PERMIT APPLICATION WITH SCOPE OF | | | WORK AND VALUE LISTED. FBC 105.1, FBC 109.3 | | | 2. EMERGENCY AND EXIT LIGHTING SHALL BE FED FROM THE | | | BRANCH CIRCUIT OF THE NORMAL LIGHTING IN THE AREA. | | | PROVIDE CORRECTION SHOWING CIRCUITS FOR THESE ITEMS. | | | NEC 700.12(F) | | | 3. CIRCUIT FOR NEW PROJECTOR AND SCREEN IS NOT | | | INDICATED OR INCLUDED IN PANEL SCHEDULE. PROVIDE | | | CORRECTION WITH CONDUCTOR AND BREAKER SIZING. NEC | | | 408.4, NEC 210.19 |
|