| 2017-09-19 14:08:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ATTACHED THE FOLLOWING ITEMS TO PLAN AS PROVISO: |
| | |
| | MAIN HOUSE: |
| | 1. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC |
| | RE3706.2, RE3902 |
| | 2. MAIN BREAKER REQUIRED AT SERVICE FOR EACH PANEL. |
| | PROVIDE CORRECTION. NEC 230.70(A); FBC RE 3601.6.2 |
| | 3. PROVIDE INTERSYSTEM BONDING TERMINATION POINT AT |
| | SERVICE. NEC 250.94; FBC RE3609.3 |
| | 4. SERVICE GROUNDING ELECTRODE TO BE AUGMENTED BY AN |
| | ADDITIONAL ELECTRODE 6 FEET AWAY OR PROVIDE EVIDENCE OF |
| | RESISTANCE TO GROUND OF 25 OHMS OR LESS. NEC 250.56; |
| | FBC RE 3608.4 |
| | 5. INCLUDE ALL GROUNDING ELECTRODES PRESENT TO BE |
| | BONDED AT SERVICE. NEC 250.50; FBC RE 3608.1 |
| | 6. SMOKE/CO ALARMS OUTSIDE OF BEDROOM SHOULD BE IN THE |
| | IMMEDIATE VICINITY OF THE SLEEPING ROOM AND INSTALLED |
| | AT THE HIGHEST POINT IN THE ROOM, AT LEAST 3 FEET FROM |
| | ANY MECHANICAL VENT OR CEILING FAN. PROVIDE CORRECTION. |
| | FBC RE 314.3; NFPA 72; 11.8.3.5 |
| | 7. LOAD CALCULATION FOR SERVICE SHOULD INCLUDE ALL |
| | LOADS, INCLUDING THE DETACHED GARAGE. A DISPOSAL IS NOT |
| | INCLUDED IN THE GENERAL LIGHTING LOAD. PROVIDE |
| | CORRECTED LOAD CALCULATION. NEC 220.82; FBC RE 3602.2 |
| | DETACHED GARAGE: |
| | 8. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| | CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| | AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| | WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; FBC |
| | RE3706.2, RE3902 |
| | 9. PROVIDE GROUNDING ELECTRODE SYSTEM AT DETACHED |
| | GARAGE AS REQUIRED FOR A BUILDING OR STRUCTURE SUPPLIED |
| | BY A FEEDER OR BRANCH CIRCUIT. NEC 250.32; FBC RE3607.3 |
| | 10. FEEDERS THAT SUPPLY A SEPARATE STRUCTURE REQUIRE A |
| | DISCONNECTING MEANS AT THE BUILDING OR SEPARATE |
| | STRUCTURE SUPPLIED. PROVIDE EITHER A MAIN DISCONNECT OR |
| | MAIN BREAKER FOR PANEL IN DETACHED GARAGE IN ADDITION |
| | TO THE MAIN BREAKER FEEDING THE PANEL. PANEL MUST BE |
| | SIZED FOR MAIN BREAKER FEEDING THIS PANEL FROM SERVICE. |
| | NEC 225.31, 225.32; FBC RE 3706.3 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |