| Plan Review Notes For Permit 17041233 |
| Permit Number |
17041233 |
|
| Review Stop |
G |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-07-18 11:19:11 | 1ST REVIEW: FBC 2014 5TH EDITION | | | | | | PLUMBING COMMENTS: | | | | | | 1. THE TANKLESS WATER HEATER ON DETACHED BUILDING IS | | | NOT SHOWN ON GAS RISER DIAGRAM PLEASE CLARIFY. PER WPB | | | AMEND TO FBC 107.2.1 | | | | | | 2. THE BTU LOAD FOR RANGE APPEARS A LITTLE LOW PLEASE | | | PROVIDE MANUFACTURE SPECS FOR ALL THE GAS APPLIANCES TO | | | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND | | | FBC-2014 FUEL GAS SEC. 402.2 | | | | | | 3. PROVIDE SIZING TABLES USED TO SIZE GAS SYSTEM. PER | | | WPB AMEND TO FBC 107.2.1 | | | | | | 4. PLEASE SHOW SHUT OFF VALVES REGULATOR AND DRIP LEGS | | | ON THE GAS RISER. PER WPB AMEND TO FBC 107.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | | THE PREVIOUSLY REVIEWED SHEETS. | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561-805-6711 | | | [email protected] | | | |
|