| 2017-08-31 09:43:10 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17041227 |
| | 8/31/17 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE AC CONTRACTOR KAREN OLIVER WHO PREPARED THE AC |
| | DESIGN ON SHEET M.1 MUST SUBMIT A SUB-PERMIT AS THE |
| | INSTALLING CONTRACTOR ON THE PROJECT- SECTION 105.3.1.2 |
| | FBC-14 BUILDING. PLEASE NOTE THAT THE EXEMPTION LISTED |
| | UNDER SECTION 105.3.1.2 SPECIFICALLY STATES THAT IN |
| | LIEU OF A PLAN DRAWN BY AN ENGINEER, THE "INSTALLING" |
| | CONTRACTOR MAY PREPARE THE DESIGN. |
| | |
| | 2) THE REQUESTED ARCHITECT'S SHOP DRAWING STAMP AND |
| | SIGNATURE FOR THE AC PLAN WAS NOT PROVIDED. |
| | |
| | 3) THE ARCHITECT OR ENGINEER OF RECORD MUST PROVIDE |
| | COMPLETE DETAILS AND DESIGN CALCULATIONS FOR |
| | INSTALLATION OF THE ROOF STAND AND CONDENSER. THE |
| | DETAILS ON M-1 ARE INCOMPLETE: A) PROVIDE DESIGN |
| | PRESSURES. B) PROVIDE A SCHEDULE TO CORRELATE THE |
| | CIRCLED NUMBERS 1-4. C) INDICATE THE STAND NOA NUMBER. |
| | D) INDICATE THE SIZE OF THE STAND LEG ANCHORING LAG |
| | BOLTS. |
| | |
| | 4) PROVIDE DUPLICATE COPIES ON THE AC AND ENERGY |
| | CALCULATIONS. ONLY ONE SET WAS SUBMITTED- SECTION |
| | 107.2.1 WPB AMENDMENTS TO THE FBC. PLEASE NOTE THAT THE |
| | DESIGN PROFESSIONAL OF RECORD MUST PLACE SHOP DRAWING |
| | STAMPS AND SIGNATURES ON THE CALCULATIONS. |
| | |