Plan Review Notes
Plan Review Notes For Permit 17041227
Permit Number 17041227
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2017-08-15 17:13:072ND REVIEW
  
  
 THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) COMPLIED
  
  
 2) SHEET 1.0 - THE EXISTING DOOR LEADING FROM THE
 OFFICE AREA TO THE NEW WAREHOUSE IS NOT INDICATED WITH
 A FIRE RATING. PER # 1 ABOVE FIRE SEPARATION RATING MAY
 BE REQUIRED.
  
 PLEASE REVIEW, CORRECT OR CLARIFY.
  
 ADDITIONAL COMMENT
  
 THE PROPOSED DOES NOT MEET THE DEFINITION OF
 ACCESSARY/INCIDENTAL USE. IN ADDITION, THE HAZARD OF
 CONTENTS SHALL BE SEPARATED AT LEAST BY 1 HOUR.
  
 6.1.14.1.3* WHERE INCIDENTAL TO ANOTHER OCCUPANCY,
 AREAS USED AS FOLLOWS SHALL BE PERMITTED TO BE
 CONSIDERED PART OF THE PREDOMINANT OCCUPANCY AND SHALL
 BE SUBJECT TO THE PROVISIONS OF THE CODE THAT APPLY TO
 THE PREDOMINANT OCCUPANCY:
 (1) MERCANTILE, BUSINESS, INDUSTRIAL, OR STORAGE USE
 (2)* NONRESIDENTIAL USE WITH AN OCCUPANT LOAD FEWER
 THAN THAT ESTABLISHED BY SECTION 6.1 FOR THE OCCUPANCY
 THRESHOLD
 (3) PORTIONS OF BUILDINGS USED AS ACCESSORY OFFICES OR
 FOR CUSTOMARY NON-HAZARDOUS USES NECESSARY FOR
 TRANSACTING THE PRINCIPAL BUSINESS IN STORAGE AND
 INDUSTRIAL OCCUPANCIES NEED NOT BE SEPARATED FROM THE
 PRINCIPAL USE.
 (4) INDUSTRIAL OCCUPANCIES PRODUCING, USING, OR STORING
 LOW HAZARD PRODUCTS IN ACCORDANCE WITH SUBDIVISION
 6.2.2 NEED NOT BE SEPARATED BY FIRE-RESISTANT
 CONSTRUCTION FROM THE OCCUPANCIES TO WHICH THEY ARE
 ACCESSORY.
  
 6.1.14.1.4 THE FOLLOWING ACCESSORY OCCUPANCIES SHALL
 NOT BE REQUIRED TO BE SEPARATED FROM THE PRIMARY
 OCCUPANCY AS REQUIRED IN 6.1.14.4:
 (1) A KITCHEN IN AN ASSEMBLY OCCUPANCY DOES NOT
 CONSTITUTE A MIXED OCCUPANCY.
 (2) ACCESSORY USES IN INDUSTRIAL AND STORAGE
 OCCUPANCIES AS OTHERWISE PROVIDED IN 6.1.14.1.3(1)
  
 (3) ROOMS OR SPACES USED FOR CUSTOMARY STORAGE OF
 NONHAZARDOUS MATERIALS IN ASSEMBLY, BUSINESS,
 EDUCATIONAL, INDUSTRIAL, MERCANTILE, HOTEL AND
 DORMITORY, AND APARTMENT OCCUPANCIES WHICH IN AGGREGATE
 DO NOT EXCEED 10% OF THE
 MAJOR FLOOR AREA IN WHICH THEY ARE LOCATED. PROTECTION
 FROM HAZARDS SHALL BE AS OTHERWISE PROVIDED IN THE
 SPECIFIC OCCUPANCY CHAPTER.
  
 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT
 DEGREES OF HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS
 OF A BUILDING OR STRUCTURE, THE MOST HAZARDOUS SHALL
 GOVERN THE CLASSIFICATION, UNLESS HAZARDOUS AREAS ARE
 SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND
 THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH 43.
  
 8.7 SPECIAL HAZARD PROTECTION.
 8.7.1 GENERAL.
 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF
 HAZARD GREATER THAN THAT NORMAL TO THE GENERAL
 OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE
 PROVIDED BY ONE OF THE FOLLOWING MEANS:
 (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT
 WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN
 ACCORDANCE WITH SECTION 8.3
 (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING
 SYSTEMS IN ACCORDANCE WITH SECTION 9.7
 (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD
 IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11
 THROUGH 43
  
 THE SEPARATION IS REQUIRED TO BE 1 HOUR FIRE RATED
 MINIMUM.
  
 PLEASE PROVIDE.
  
 3) COMPLIED
  
  
 4) COMPLIED
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]