| 2017-08-15 17:13:07 | 2ND REVIEW |
| | |
| | |
| | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) COMPLIED |
| | |
| | |
| | 2) SHEET 1.0 - THE EXISTING DOOR LEADING FROM THE |
| | OFFICE AREA TO THE NEW WAREHOUSE IS NOT INDICATED WITH |
| | A FIRE RATING. PER # 1 ABOVE FIRE SEPARATION RATING MAY |
| | BE REQUIRED. |
| | |
| | PLEASE REVIEW, CORRECT OR CLARIFY. |
| | |
| | ADDITIONAL COMMENT |
| | |
| | THE PROPOSED DOES NOT MEET THE DEFINITION OF |
| | ACCESSARY/INCIDENTAL USE. IN ADDITION, THE HAZARD OF |
| | CONTENTS SHALL BE SEPARATED AT LEAST BY 1 HOUR. |
| | |
| | 6.1.14.1.3* WHERE INCIDENTAL TO ANOTHER OCCUPANCY, |
| | AREAS USED AS FOLLOWS SHALL BE PERMITTED TO BE |
| | CONSIDERED PART OF THE PREDOMINANT OCCUPANCY AND SHALL |
| | BE SUBJECT TO THE PROVISIONS OF THE CODE THAT APPLY TO |
| | THE PREDOMINANT OCCUPANCY: |
| | (1) MERCANTILE, BUSINESS, INDUSTRIAL, OR STORAGE USE |
| | (2)* NONRESIDENTIAL USE WITH AN OCCUPANT LOAD FEWER |
| | THAN THAT ESTABLISHED BY SECTION 6.1 FOR THE OCCUPANCY |
| | THRESHOLD |
| | (3) PORTIONS OF BUILDINGS USED AS ACCESSORY OFFICES OR |
| | FOR CUSTOMARY NON-HAZARDOUS USES NECESSARY FOR |
| | TRANSACTING THE PRINCIPAL BUSINESS IN STORAGE AND |
| | INDUSTRIAL OCCUPANCIES NEED NOT BE SEPARATED FROM THE |
| | PRINCIPAL USE. |
| | (4) INDUSTRIAL OCCUPANCIES PRODUCING, USING, OR STORING |
| | LOW HAZARD PRODUCTS IN ACCORDANCE WITH SUBDIVISION |
| | 6.2.2 NEED NOT BE SEPARATED BY FIRE-RESISTANT |
| | CONSTRUCTION FROM THE OCCUPANCIES TO WHICH THEY ARE |
| | ACCESSORY. |
| | |
| | 6.1.14.1.4 THE FOLLOWING ACCESSORY OCCUPANCIES SHALL |
| | NOT BE REQUIRED TO BE SEPARATED FROM THE PRIMARY |
| | OCCUPANCY AS REQUIRED IN 6.1.14.4: |
| | (1) A KITCHEN IN AN ASSEMBLY OCCUPANCY DOES NOT |
| | CONSTITUTE A MIXED OCCUPANCY. |
| | (2) ACCESSORY USES IN INDUSTRIAL AND STORAGE |
| | OCCUPANCIES AS OTHERWISE PROVIDED IN 6.1.14.1.3(1) |
| | |
| | (3) ROOMS OR SPACES USED FOR CUSTOMARY STORAGE OF |
| | NONHAZARDOUS MATERIALS IN ASSEMBLY, BUSINESS, |
| | EDUCATIONAL, INDUSTRIAL, MERCANTILE, HOTEL AND |
| | DORMITORY, AND APARTMENT OCCUPANCIES WHICH IN AGGREGATE |
| | DO NOT EXCEED 10% OF THE |
| | MAJOR FLOOR AREA IN WHICH THEY ARE LOCATED. PROTECTION |
| | FROM HAZARDS SHALL BE AS OTHERWISE PROVIDED IN THE |
| | SPECIFIC OCCUPANCY CHAPTER. |
| | |
| | 6.2.1.3* FOR THE PURPOSE OF THIS CODE, WHERE DIFFERENT |
| | DEGREES OF HAZARD OF CONTENTS EXIST IN DIFFERENT PARTS |
| | OF A BUILDING OR STRUCTURE, THE MOST HAZARDOUS SHALL |
| | GOVERN THE CLASSIFICATION, UNLESS HAZARDOUS AREAS ARE |
| | SEPARATED OR PROTECTED AS SPECIFIED IN SECTION 8.7 AND |
| | THE APPLICABLE SECTIONS OF CHAPTERS 11 THROUGH 43. |
| | |
| | 8.7 SPECIAL HAZARD PROTECTION. |
| | 8.7.1 GENERAL. |
| | 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF |
| | HAZARD GREATER THAN THAT NORMAL TO THE GENERAL |
| | OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE |
| | PROVIDED BY ONE OF THE FOLLOWING MEANS: |
| | (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT |
| | WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN |
| | ACCORDANCE WITH SECTION 8.3 |
| | (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING |
| | SYSTEMS IN ACCORDANCE WITH SECTION 9.7 |
| | (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD |
| | IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 |
| | THROUGH 43 |
| | |
| | THE SEPARATION IS REQUIRED TO BE 1 HOUR FIRE RATED |
| | MINIMUM. |
| | |
| | PLEASE PROVIDE. |
| | |
| | 3) COMPLIED |
| | |
| | |
| | 4) COMPLIED |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |