| Plan Review Notes For Permit 17041227 |
| Permit Number |
17041227 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-03 10:45:51 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041227 | | | 5/3/17 | | | | | | 1) SUBMIT ENERGY CALCULATIONS FOR THE ADDITION- SECTION | | | C101.4.3 FBC-14 ENERGY CONSERVATION. | | | | | | 2) SUBMIT AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW SYSTEM- SECTION C403.2.1. | | | | | | 3) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF | | | THE EXTERIOR CONDENSER- SECTION 301.15. | | | | | | 4) AUTOMATIC FUNCTIONING OF THE O/A DAMPER IS REQUIRED | | | PER SECTION C403.2.2 | | | | | | 5) PROVIDE A MECHANICAL SUB-PERMIT APPLICATION FROM | | | K.O. ENERGY DESIGN IF THEY ARE THE INSTALLING | | | CONTRACTOR. IF K.O. IS NOT THE INSTALLING CONTRACTOR | | | THEN THE PLANS MUST HAVE SHOP DRAWING APPROVAL BY THE | | | ARCHITECT OF RECORD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|