Plan Review Notes
Plan Review Notes For Permit 17041227
Permit Number 17041227
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-05-04 12:58:12THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SP 1 - A INDUSTRIAL ZONING IS INDICATED; HOWEVER,
 THE OCCUPANCY CLASSIFICATION PER NFPA 101 IS NOT.
  
 6.1 CLASSIFICATION OF OCCUPANCY.
 6.1.1 GENERAL.
 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A
 BUILDING OR STRUCTURE, OR PORTION OF A BUILDING OR
 STRUCTURE, SHALL BE CLASSIFIED IN ACCORDANCE WITH 6.1.2
 THROUGH 6.1.13. OCCUPANCY CLASSIFICATION SHALL BE
 SUBJECT TO THE RULING OF THE AUTHORITY HAVING
 JURISDICTION WHERE THERE IS A QUESTION OF PROPER
 CLASSIFICATION IN ANY INDIVIDUAL CASE.
  
 6.1.14 MULTIPLE OCCUPANCIES.
 6.1.14.1 GENERAL.
 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE
 REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING:
 (1) MIXED OCCUPANCIES ? 6.1.14.3
 (2) SEPARATED OCCUPANCIES ? 6.1.14.4
  
 WHAT IS THE OCCUPANCY CLASSIFICATION AND IS IT MIXED OR
 SEPARATED.
  
  
  
 2) SHEET 1.0 - THE EXISTING DOOR LEADING FROM THE
 OFFICE AREA TO THE NEW WAREHOUSE IS NOT INDICATED WITH
 A FIRE RATING. PER # 1 ABOVE FIRE SEPARATION RATING MAY
 BE REQUIRED.
  
 PLEASE REVIEW, CORRECT OR CLARIFY.
  
  
  
 3) SHEET E 1.0 - THERE IS NOT EXIT SIGN AT THE NEW
 WAREHOUSE MAN DOOR. AN EXIT IS REQUIRED FROM THIS NEW
 SPACE AND IT IS REQUIRED TO BE ILLUMINATED.
  
 PLEASE REVIEW, CORRECT OR CLARITY.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  