| 2017-07-27 09:36:54 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. RISER DIAGRAM PROVIDED SHOWS THREE 4/0 THHN IN 1 1/2 |
| | CONDUIT. A 1 1/2 CONDUIT IS CAPABLE OF ONLY TWO OF THIS |
| | SIZE WIRE PER THE ANNEX C TABLES. PROVIDE CORRECTION. |
| | IDENTIFY IF THIS WIRE IS COPPER OR ALUMINUM. NEC ANNEX |
| | C, FBC 107.2.1 |
| | 2. RISER DIAGRAM ALSO SHOWS WHAT APPEARS TO BE 3 WIRES |
| | FEEDING THE INTERIOR PANEL WITH A SEPARATE GROUND WIRE |
| | GOING TO PANEL. THE EGC SHOULD BE IN THE SAME CONDUIT |
| | AS THE POWER WIRES. PROVIDE CORRECTION. NEC 250.118, |
| | 250.122; FBC RE3908.8 |
| | 3. ELECTRICAL PLAN SHOWS DIFFERENT LOCATION OF AHU-1 |
| | AND AHU-2 THAN THE MECHANICAL PLAN SHOWS. PROVIDE |
| | CORRECTION WHERE NECESSARY. FBC 107.2.1 |
| | 4. SPECS FOR TANKLESS WATER HEATER PROVIDED SHOW THAT |
| | THE UNIT REQUIRES TWO 50 AMP CIRCUITS WITH #6 CU WIRE. |
| | PANEL SCHEDULE SHOWS WHAT APPEARS TO BE ONE CIRCUIT |
| | WITH #2 WIRE, THE BREAKER IS NOT IDENTIFIED. PROVIDE |
| | CORRECTION FOR THIS CIRCUIT, ALSO SHOW BREAKER SIZES |
| | FOR THE EVEN NUMBER CIRCUITS THAT ARE MISSING. NEC |
| | 110.3, NEC 215.2, 215.5, 408.4; FBC RE3706.2 |
| | 5. NEW SUBMISSION SHOWS PANEL B IN THE STORAGE AREA, |
| | BUT NO DETAILS OF CIRCUITS OR PANEL SCHEDULE INCLUDED. |
| | PROVIDE PANEL SCHEDULE, SHOW GFCI PROTECTION OF OUTLETS |
| | FOR A STORAGE BUILDING. NEC 210.8(A)(2), 215.5, 408.4; |
| | FBC RE3706.2, RE3902.2 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |