Plan Review Notes
Plan Review Notes For Permit 17041218
Permit Number 17041218
Review Stop Z
Sequence Number 2
Notes
Date Text
2017-06-28 16:01:53** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) NEED UPDATED SURVEY OF THE PROPERTY. [5/24/2017
 REPEAT COMMENT]
  
 2.) SHOW SETBACK DISTANCE FROM THE NEW A/C UNITS TO THE
 PROPERTY LINE(S). [5/24/2017 REPEAT COMMENT]
  
 3.) WHAT IS THE SETBACK DISTANCE FROM THE PROPOSED
 ADDITION TO THE EAST (REAR) PROPERTY LINE? PLEASE
 PROVIDE DIMENSIONS IN THE PLANS.
  
 4.) NORTH ELEVATION IS INCONSISTENT WITH THE FLOOR
 PLAN. PLEASE ADDRESS FOR CONSISTENCY.
  
  
 NOTES:
  
 * ZONE: SF7
  
 * CORNER PROPERTY. PER ZLDR S.94-611, OLIVE ST. IS
 DEFINED AS THE FRONT LOT LINE.
  
 * SCOPE OF WORK IS LESS THAN 50% OF THE VALUE OF THE
 EXISTING BUILDING.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  