2017-07-10 11:27:58CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (2ND REVIEW):
  
 1. PLANS NOT SEALED AS REQUIRED PER FLORIDA STATUTES.
 FS471, FAC61G15-23.
 2. SHEET A1.0 SHOWS A NEW OVERHEAD SERVICE DROP FROM
 FPL. PROVIDE CLEARANCE ABOVE ROOF PER CODE. NEC
 230.24(A); FBC RE3604.2.1
 3. PANEL NOTE #1 REFERENCES THE PANEL SCHEDULE SHOWN,
 HOWEVER, THERE IS NO PANEL SCHEDULE PROVIDED. PROVIDE
 PANEL SCHEDULE, INDICATING WIRE AND BREAKER SIZE FOR
 EACH CIRCUIT. NEC 215.5; FBC RE3706.2
 4. PANEL NOTE #2 STATES THAT THERE WILL BE A 1/0
 ALUMINUM(AL) SERVICE CONDUCTOR. 1/0 AL IS NOT RATED FOR
 THE SPECIFIED SERVICE CAPACITY. PROVIDE CORRECTION. NEC
 310.15; NEC 215.2; FBC RE3602.1
 5. PROVIDE DETAIL OF CIRCUITS TO STORAGE BUILDING. PER
 CODE: "A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY
 A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A
 SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY
 ONE FEEDER OR BRANCH CIRCUIT". NEC 225.30; FBC 107.2.1
 6. PROVIDE ACCURATE LOAD CALCULATION. THE LOAD
 CALCULATION PROVIDED HAS ITEMS INCLUDED THAT SHOULD NOT
 BE, SUCH AS LIGHTING AND FANS WHICH WOULD ALREADY BE
 INCLUDED IN THE GENERAL LIGHTING LOAD BASED ON SQUARE
 FOOTAGE. SOME ITEMS ARE MISSING, SUCH AS THE LAUNDRY
 CIRCUIT AND THE DRYER LOAD. THE VOLTAGE USED FOR
 CALCULATION SHOULD BE 240. MATH IS INCORRECT. NEC
 220.5; NEC 220; FBC RE3602.2
 7. PROVIDE LIGHTING AND OUTLET FOR AHU2 IN ATTIC. FBC
 RM1305.1.3.1
 8. PLAN SHOWS A 200 AMP DISCONNECT FEEDING A 250 AMP
 PANEL. PROVIDE CORRECTION, MATCHING DISCONNECT AND
 PANEL TO REQUIRED LOAD CALCULATED. NEC 220; FBC
 RE3602.3
 9. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER. NEC
 110.3
 10. SHOW ON PLAN ALL OUTLETS REQUIRED PER NEC 210.52
 FOR WALL SPACE. NEC 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  