| 2017-07-10 11:27:58 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS (2ND REVIEW): |
| | |
| | 1. PLANS NOT SEALED AS REQUIRED PER FLORIDA STATUTES. |
| | FS471, FAC61G15-23. |
| | 2. SHEET A1.0 SHOWS A NEW OVERHEAD SERVICE DROP FROM |
| | FPL. PROVIDE CLEARANCE ABOVE ROOF PER CODE. NEC |
| | 230.24(A); FBC RE3604.2.1 |
| | 3. PANEL NOTE #1 REFERENCES THE PANEL SCHEDULE SHOWN, |
| | HOWEVER, THERE IS NO PANEL SCHEDULE PROVIDED. PROVIDE |
| | PANEL SCHEDULE, INDICATING WIRE AND BREAKER SIZE FOR |
| | EACH CIRCUIT. NEC 215.5; FBC RE3706.2 |
| | 4. PANEL NOTE #2 STATES THAT THERE WILL BE A 1/0 |
| | ALUMINUM(AL) SERVICE CONDUCTOR. 1/0 AL IS NOT RATED FOR |
| | THE SPECIFIED SERVICE CAPACITY. PROVIDE CORRECTION. NEC |
| | 310.15; NEC 215.2; FBC RE3602.1 |
| | 5. PROVIDE DETAIL OF CIRCUITS TO STORAGE BUILDING. PER |
| | CODE: "A BUILDING OR OTHER STRUCTURE THAT IS SERVED BY |
| | A BRANCH CIRCUIT OR FEEDER ON THE LOAD SIDE OF A |
| | SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED BY ONLY |
| | ONE FEEDER OR BRANCH CIRCUIT". NEC 225.30; FBC 107.2.1 |
| | 6. PROVIDE ACCURATE LOAD CALCULATION. THE LOAD |
| | CALCULATION PROVIDED HAS ITEMS INCLUDED THAT SHOULD NOT |
| | BE, SUCH AS LIGHTING AND FANS WHICH WOULD ALREADY BE |
| | INCLUDED IN THE GENERAL LIGHTING LOAD BASED ON SQUARE |
| | FOOTAGE. SOME ITEMS ARE MISSING, SUCH AS THE LAUNDRY |
| | CIRCUIT AND THE DRYER LOAD. THE VOLTAGE USED FOR |
| | CALCULATION SHOULD BE 240. MATH IS INCORRECT. NEC |
| | 220.5; NEC 220; FBC RE3602.2 |
| | 7. PROVIDE LIGHTING AND OUTLET FOR AHU2 IN ATTIC. FBC |
| | RM1305.1.3.1 |
| | 8. PLAN SHOWS A 200 AMP DISCONNECT FEEDING A 250 AMP |
| | PANEL. PROVIDE CORRECTION, MATCHING DISCONNECT AND |
| | PANEL TO REQUIRED LOAD CALCULATED. NEC 220; FBC |
| | RE3602.3 |
| | 9. PROVIDE SPEC SHEET FOR TANKLESS WATER HEATER. NEC |
| | 110.3 |
| | 10. SHOW ON PLAN ALL OUTLETS REQUIRED PER NEC 210.52 |
| | FOR WALL SPACE. NEC 210.52; FBC RE3901.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |