2017-05-24 13:36:48** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) NEED UPDATED SURVEY OF THE PROPERTY.
  
 2.) REAR BUILDING SETBACK DOES NOT MEET THE MINIMUM
 REQUIREMENT OF THE ZONING CODE. THE MINIMUM REQUIRED
 REAR SETBACK IS 12.5 FT. ONLY 5 FT. HAS BEEN PROVIDED
 FOR THE REAR SETBACK. PLEASE ADDRESS. NOTE: THE
 EXISTING CARPORT DOES NOT MEET CURRENT SETBACK
 REQUIREMENT AND CANNOT BE ENCLOSED. [ZLDR
 S.94-74(A)(2)]
  
 3.) SHOW SETBACK DISTANCE FROM THE NEW A/C UNITS TO THE
 PROPERTY LINE(S).
  
 4.) WEST ELEVATION IS MISSING FOR THE EXITING STORAGE
 BUILDING. PLEASE ADDRESS.
  
  
 NOTES:
  
 * ZONE: SF7
  
 * CORNER PROPERTY. PER ZLDR S.94-611, OLIVE ST. IS
 DEFINED AS THE FRONT LOT LINE.
  
 * SCOPE OF WORK IS LESS THAN 50% OF THE VALUE OF
 EXISTING BUILDING.
  
 * REVISION MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.