2017-05-03 10:45:342010 FBC - RESIDENTIAL
 REVISION IS DENIED
  
 1) THE PERMIT AND PLANS THAT YOU ARE REVISING ARE UNDER
 THE 2010 FLORIDA BUILDING CODE. THE REVISED PLANS
 REFERENCE THE 2014 FBC. YOU ARE NOT ALLOWED TO MIX
 DIFFERENT EDITIONS OF THE BUILDING CODE. PLEASE CORRECT
 THE REVISED PLANS TO REFERENCE THE 2010 FBC. FLORIDA
 STATUTES CHAPTER 553
  
 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE EXTERIOR DOOR.
  
 3) SHOW THE CONNECTORS THAT WILL PROVIDE THE CONTINOUS
 LOAD PATH FROM THE ROOF TO THE FOUNDATION ON THE
 FRAMING PLAN. FBC-R301.1
  
 4) THE TITLE BLOCK OF THE PLANS THAT WERE SIGNED AND
 SEALED BY THE ENGINEER HAS BEEN ALTERED BY PASTING
 PAPER ONTO THEM. FS 471