| 2017-05-03 10:45:34 | 2010 FBC - RESIDENTIAL | | | REVISION IS DENIED | | | | | | 1) THE PERMIT AND PLANS THAT YOU ARE REVISING ARE UNDER | | | THE 2010 FLORIDA BUILDING CODE. THE REVISED PLANS | | | REFERENCE THE 2014 FBC. YOU ARE NOT ALLOWED TO MIX | | | DIFFERENT EDITIONS OF THE BUILDING CODE. PLEASE CORRECT | | | THE REVISED PLANS TO REFERENCE THE 2010 FBC. FLORIDA | | | STATUTES CHAPTER 553 | | | | | | 2) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS | | | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC | | | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE | | | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER | | | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH | | | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS | | | AND MAXIMUM DESIGN PRESSURES FOR THE EXTERIOR DOOR. | | | | | | 3) SHOW THE CONNECTORS THAT WILL PROVIDE THE CONTINOUS | | | LOAD PATH FROM THE ROOF TO THE FOUNDATION ON THE | | | FRAMING PLAN. FBC-R301.1 | | | | | | 4) THE TITLE BLOCK OF THE PLANS THAT WERE SIGNED AND | | | SEALED BY THE ENGINEER HAS BEEN ALTERED BY PASTING | | | PAPER ONTO THEM. FS 471 |
|