| 2017-05-01 17:01:28 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET A 250 - THERE IS AN INCORRECT REFERNECE TO THE |
| | NFPA AND FLORIDA FIRE PREVENTION CODE. THOUGH THE 5TH |
| | EDITION IS CORRECT THE YEAR IS NOT. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE EFFECTIVE |
| | DECEMBER 31, 2014, (2014) INCLUDING THE 2012 EDITION OF |
| | NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR |
| | STANDARDS. |
| | |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | |
| | 2) SHEET A 250 - THERE IS A REFERENCE OF THE OCCUPANY |
| | CLASSIFICATION OF BUSINESS AND ANOTHER INDICATING |
| | STORAGE. IS THIS A MIXED OR SEPARATED OCCUPANCY. |
| | |
| | PER NFPA 101, CHAPTER 6, OCCUPANCY CLASSIFICATIONS. |
| | |
| | 6.1.14 MULTIPLE OCCUPANCIES. |
| | 6.1.14.1 GENERAL. |
| | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING: |
| | (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| | |
| | 6.1.14.2 DEFINITIONS. |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE |
| | RESISTANCE?RATED ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1 |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, |
| | UNLESS SEPARATE SAFEGUARDS ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE BUILDING COMPRISING A DISTINCT |
| | OCCUPANCY, AS DESCRIBED IN THIS CHAPTER, SHALL BE |
| | COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, |
| | 6.1.14.4.3, TABLE 6.1.14.4.1(A), AND TABLE |
| | 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED BY |
| | APPROVED EXISTING SEPARATIONS. |
| | |
| | PLEASE REVIEW, CLARIFY, CORRECT AND ENSURE COMPLIANCE. |
| | |
| | |
| | |
| | |
| | 3) SHEET A 201 - THERE IS A NEW DOOR, 106, INDICATED |
| | THROUGH THE WALL TO THE STORAGE AREA. THERE IS NOT FIRE |
| | RATING INDICATED ON THIS EXISTING WALL. A PREVIOUS |
| | BUILDING PERMIT PLAN INDICATED THAT THIS IS A 2 HOUR |
| | FIRE RATED WALL. |
| | |
| | PLEASE REVIEW WITH # 2 ABOVE AND DPROVIDE THE |
| | APPLICABLE RATING TO THIS OPENING. |
| | |
| | |
| | |
| | |
| | 4) SHEET A 250 - THERE IS A REFERENCE INDICATED TO NFPA |
| | 101 7.3.1.2 IN THE OCCUPANCY LOAD TABULATION TO |
| | BUSINESS USE 1 PER 300 SQ FT. |
| | |
| | PER NFPA 101, CHAPTER 7 MEANS OF EGRESS, |
| | |
| | 7.3.1.2* OCCUPANT LOAD FACTOR. THE OCCUPANT LOAD IN ANY |
| | BUILDING OR PORTION THEREOF SHALL BE NOT LESS THAN THE |
| | NUMBER OF PERSONS DETERMINED BY DIVIDING THE FLOOR AREA |
| | ASSIGNED TO THAT USE BY THE OCCUPANT LOAD FACTOR FOR |
| | THAT USE AS SPECIFIED IN TABLE7.3.1.2, FIGURE 7.3.1.2 |
| | (A), AND FIGURE 7.3.1.2 |
| | (B). WHERE BOTH GROSS AND NET AREA FIGURES ARE GIVEN |
| | FOR THE SAME OCCUPANCY, CALCULATIONS SHALL BE MADE BY |
| | APPLYING THE GROSS AREA FIGURE TO THE GROSS AREA OF THE |
| | PORTION OF THE BUILDING DEVOTED TO THE USE FOR WHICH |
| | THE GROSS AREA FIGURE IS SPECIFIED AND BY APPLYING THE |
| | NET AREA FIGURE TO THE NET AREA OF THE PORTION OF THE |
| | BUILDING DEVOTED TO THE USE FOR WHICH THE NET AREA |
| | FIGURE IS SPECIFIED. |
| | |
| | TABLER 7.3.1.2 INDICATES 1 PER 100 SQ FT. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | 5) SHEET A 250 - THERE ARE TWO OCCUPANCY CALCULATIONS |
| | INDICATED, BUSINESS 25 AND STORAGE 5, AND A TOTAL |
| | INDICATED AS 25. THE TOTAL SHOULD READ 26. |
| | |
| | PLEASE CORRECT. |
| | |
| | |
| | |
| | |
| | 6) SHEET A 601 - THE DOOR SCHEDULE DOES NOT INDICATE A |
| | FIRE RATING FOR DOOR 106. |
| | |
| | PLEASE REVIEW # 2 AND # 3 ABOVE AND INDICATE AS |
| | APPLICABLE. |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |