| 2017-05-03 13:56:02 | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | |
| | PROVISO PROVIDE THE FOLLOWING INFORMATION PRIOR TO THE |
| | FIANL ELECTRICAL INSPECTION.. |
| | |
| | |
| | |
| | FBC_EC405.2.2.2 OCCUPANCY SENSORS. |
| | OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS, |
| | CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK |
| | ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND |
| | JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET |
| | (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT |
| | PARTITIONS. THESE AUTOMATIC CONTROL DEVICES SHALL BE |
| | INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30 |
| | MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL |
| | EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO |
| | AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50 |
| | PERCENT POWER. |
| | |
| | FBC-EC405.2.4 EXTERIOR LIGHTING CONTROLS. |
| | LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION |
| | SHALL BE CONTROLLED BY EITHER A COMBINATION OF A |
| | PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME |
| | SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION |
| | SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR |
| | PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF |
| | RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS |
| | OF POWER FOR A PERIOD OF AT LEAST 10 HOURS. |
| | |
| | C405.5.2 INTERIOR LIGHTING POWER. |
| | THE TOTAL INTERIOR LIGHTING POWER ALLOWANCE (WATTS) IS |
| | DETERMINED ACCORDING TO TABLE C405.5.2(1) USING THE |
| | BUILDING AREA METHOD, OR TABLE C405.5.2(2) USING THE |
| | SPACE-BY-SPACE METHOD, FOR ALL AREAS OF THE BUILDING |
| | COVERED IN THIS PERMIT. FOR THE BUILDING AREA METHOD, |
| | THE INTERIOR LIGHTING POWER ALLOWANCE IS THE FLOOR AREA |
| | FOR EACH BUILDING AREA TYPE LISTED IN TABLE C405.5.2(1) |
| | TIMES THE VALUE FROM TABLE C405.5.2(1) FOR THAT AREA. |
| | FOR THE PURPOSES OF THIS METHOD, AN ?AREA? SHALL BE |
| | DEFINED AS ALL CONTIGUOUS SPACES THAT ACCOMMODATE OR |
| | ARE ASSOCIATED WITH A SINGLE BUILDING AREA TYPE AS |
| | LISTED IN TABLE C405.5.2(1). WHERE THIS METHOD IS USED |
| | TO CALCULATE THE TOTAL INTERIOR LIGHTING POWER FOR AN |
| | ENTIRE BUILDING, EACH BUILDING AREA TYPE SHALL BE |
| | TREATED AS A SEPARATE AREA. FOR THE SPACE-BY-SPACE |
| | METHOD, THE INTERIOR LIGHTING POWER ALLOWANCE IS |
| | DETERMINED BY MULTIPLYING THE FLOOR AREA OF EACH SPACE |
| | TIMES THE VALUE FOR THE SPACE TYPE IN TABLE C405.5.2(2) |
| | THAT MOST CLOSELY REPRESENTS THE PROPOSED USE OF THE |
| | SPACE, AND THEN SUMMING THE LIGHTING POWER ALLOWANCES |
| | FOR ALL SPACES. TRADEOFFS AMONG SPACES ARE PERMITTED. |
| | |