Plan Review Notes
Plan Review Notes For Permit 17041203
Permit Number 17041203
Review Stop E
Sequence Number 1
Notes
Date Text
2017-05-03 13:56:02JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 PROVISO PROVIDE THE FOLLOWING INFORMATION PRIOR TO THE
 FIANL ELECTRICAL INSPECTION..
  
  
  
 FBC_EC405.2.2.2 OCCUPANCY SENSORS.
 OCCUPANCY SENSORS SHALL BE INSTALLED IN ALL CLASSROOMS,
 CONFERENCE/MEETING ROOMS, EMPLOYEE LUNCH AND BREAK
 ROOMS, PRIVATE OFFICES, RESTROOMS, STORAGE ROOMS AND
 JANITORIAL CLOSETS, AND OTHER SPACES 300 SQUARE FEET
 (28 M2) OR LESS ENCLOSED BY FLOOR-TO-CEILING HEIGHT
 PARTITIONS. THESE AUTOMATIC CONTROL DEVICES SHALL BE
 INSTALLED TO AUTOMATICALLY TURN OFF LIGHTS WITHIN 30
 MINUTES OF ALL OCCUPANTS LEAVING THE SPACE, AND SHALL
 EITHER BE MANUAL ON OR SHALL BE CONTROLLED TO
 AUTOMATICALLY TURN THE LIGHTING ON TO NOT MORE THAN 50
 PERCENT POWER.
  
 FBC-EC405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 C405.5.2 INTERIOR LIGHTING POWER.
 THE TOTAL INTERIOR LIGHTING POWER ALLOWANCE (WATTS) IS
 DETERMINED ACCORDING TO TABLE C405.5.2(1) USING THE
 BUILDING AREA METHOD, OR TABLE C405.5.2(2) USING THE
 SPACE-BY-SPACE METHOD, FOR ALL AREAS OF THE BUILDING
 COVERED IN THIS PERMIT. FOR THE BUILDING AREA METHOD,
 THE INTERIOR LIGHTING POWER ALLOWANCE IS THE FLOOR AREA
 FOR EACH BUILDING AREA TYPE LISTED IN TABLE C405.5.2(1)
 TIMES THE VALUE FROM TABLE C405.5.2(1) FOR THAT AREA.
 FOR THE PURPOSES OF THIS METHOD, AN ?AREA? SHALL BE
 DEFINED AS ALL CONTIGUOUS SPACES THAT ACCOMMODATE OR
 ARE ASSOCIATED WITH A SINGLE BUILDING AREA TYPE AS
 LISTED IN TABLE C405.5.2(1). WHERE THIS METHOD IS USED
 TO CALCULATE THE TOTAL INTERIOR LIGHTING POWER FOR AN
 ENTIRE BUILDING, EACH BUILDING AREA TYPE SHALL BE
 TREATED AS A SEPARATE AREA. FOR THE SPACE-BY-SPACE
 METHOD, THE INTERIOR LIGHTING POWER ALLOWANCE IS
 DETERMINED BY MULTIPLYING THE FLOOR AREA OF EACH SPACE
 TIMES THE VALUE FOR THE SPACE TYPE IN TABLE C405.5.2(2)
 THAT MOST CLOSELY REPRESENTS THE PROPOSED USE OF THE
 SPACE, AND THEN SUMMING THE LIGHTING POWER ALLOWANCES
 FOR ALL SPACES. TRADEOFFS AMONG SPACES ARE PERMITTED.
  