Date Text
2017-05-03 15:52:372014 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17041203
 ADD: 719 N. DIXIE HWY.
 CONT: THE EVERGLADES GROUP
 TEL: 561-912-0400
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. MAY 03/2017
 ACTION: DENIED
  
 1) THE COVERSHEET CS-1 DESIGN IS BASED ON;
 2014 EXIST. BUILDING CODE ALTERATION LEVEL III
 ASCE 7-10
 185 MPH VULT 3 SECOND GUST
 STRUCTURE CATEGORY II, EXPOSURE C
 1A) THE DESIGNER OF RECORD CAN DESIGN TO THE MORE
 STRINGENT 185 MPH VULT, WIND SPEED MAPS SHOW A WIND
 SPEED OF 170 VULT, SEE FIGURE 1609A.
  
 1B) THE COVERSHEET LIST THIS ALTERATION AS A LEVEL III
 ALTERATION. THE DESIGNER OF RECORD HAS NOT DECLARED IF
 THE ALTERATION IS DESIGNED AS AN SUBSTANTIAL STRUCTURAL
 ALTERATION 907.4.2 OR 907.4.3 LIMITED STRUCTURAL
 ALTERATION, MUST ALSO COMPLY WITH 807.5. ALSO SEE THE
 REQUIREMENTS UNDER 907.4.1 EVALUATION AND ANALYSIS.
  
 2) THE LIFE SAFETY SHEET INDICATES THE BUILDING BEING
 3350 SQ. FT. 2091 SQ. FT. OF BUSINESS OCCUPANCY AND
 1259 STORAGE OCCUPANCY. THE STORAGE OCCUPANCY IS 0.37 %
 OF THE FLOOR AREA OR OVER 10% OF THE FLOOR AREA MAKING
 THIS MIXED USE OCCUPANCY BETWEEN BUSINESS AND STORAGE
 OCCUPANCIES, SEE FBC-B 508.2.1 AREA LIMITATIONS.
  
 2A) THE DESIGNER OF RECORD HAS NOT DECLARED THE TYPE OF
 STORAGE OCCUPANCY S1 OR S2 THE TYPES OF MATERIALS TO BE
 STORED AND IF SEPARATION OF OCCUPANCIES IS REQUIRED BY
 FBC-B TABLE 508.4. PLEASE ALSO REVIEW SECTIONS 508.3
 NONSEPARATED OCCUPANCIES AND 508.3.3 SEPARATION.
  
 2B) IF THE OCCUPANCY SEPARATION WALL BETWEEN THE
 STORAGE AND BUSINESS OCCUPANCIES IS DECLARED TO BE
 REQUIRED FIRE RATED THEN THE DOOR 106 WILL HAVE TO HAVE
 OPENING PROTECTIVES IN COMPLIANCE WITH 2014 FBC-B TABLE
 716.5. SHEET A601 THE DOOR SCHEDULE DOES NOT HAVE A
 COLUMN FOR THE FIRE RATING OF DOOR & JAMBS.
  
 2C) CODE ANALYSIS LIST THE BUSINESS OCCUPANCY OF 2091
 SQ. FT./ 100= 21 OCCUPANTS AND THE STORAGE OCCUPANCY
 1259 SQ. FT./ 300=5 OCCUPANTS. 21+5=26 OCCUPANTS NOT
 25. PLEASE UPDATE PLAN, TYPO.
 107.2.1.3 ADDITIONAL INFORMATION REQUIRED.
  
 2D) THE FLOOR PLANS DO NOT INDICATE IF THE EXISTING
 EXTERIOR DOORS HAVE LEVEL WALKING SURFACES TO BE ABLE
 TO GAIN ENTRY INTO THE TENANT SPACE. 403.1. WALKING
 SURFACES THAT ARE A PART OF AN ACCESSIBLE ROUTE SHALL
 COMPLY WITH 403.
  
  
 3) SHEET A601 THE RESTROOM DETAILS, PLEASE NOTE THE
 GRAB BARS FOR THE WATER CLOSET ARE MEASURED AT THE
 CENTERLINE, PLEASE NOTE THE 2014 FBC-ACCESSIBILITY CODE
 SECTION 609.4 TAKES THE MEASUREMENTS FROM THE FINISH
 FLOOR TO THE TOP OF THE GRASPABLE SURFACE. 900 SERIES
 OF ADA DRAWINGS THE HEIGHT IS NOT GIVEN.
  
 3A) THERE IS NO DETAILS FOR THE HEIGHT OF THE RECEPTION
 FRONT COUNTER SHOWING COMPLIANCE WITH 2014 FBC-ACCESS.
 CODE 904.3.3 CHECK WRITING SURFACES. WHERE PROVIDED,
 CHECK WRITING SURFACES SHALL COMPLY WITH 902.3.
 902.3 HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 3B) THE PLANS ARE ALSO MISSING DETAILS ON THE BREAK
 ROOM SINK AND HEIGHT OF THE COUNTERTOP. ACCESS.
 CODE 606.2 CLEAR FLOOR SPACE, & 606.3 HEIGHTS.
 LAVATORIES AND SINKS SHALL BE INSTALLED WITH THE FRONT
 OF THE HIGHER OF THE RIM OR COUNTER SURFACE 34 INCHES
 (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES