| 2017-05-25 09:33:51 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE SITE PLAN AND SURVEY DO NOT MATCH. FBC 107.2.1 |
| | ZONING COMMENTS MUST BE ADDRESSED. |
| | |
| | 2) SPECIFY THE ROOF SHEATHING AND FASTENING |
| | REQUIREMENTS ON THE PLANS. FBC-R803.2 AND 803.2.3.1 |
| | |
| | 3) CLARIFY THE EXPOSURE CATEGORY THAT IS LISTED ON |
| | SHEET S000. IT IS NOT CLEAR ON THE PLANS IF IT IS D OR |
| | C. FBC-R301.2.1.4 |
| | |
| | 4) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, WINDOW/GLASS TYPES, STRUCTURAL |
| | MULLIONS AND EXTERIOR DOOR TYPES. SUBMIT TWO SETS OF |
| | PRODUCT APPROVALS FOR THE EXTERIOR METAL LOUVER PANELS |
| | AND DOORS OR REQUEST THAT THE SUBMITTALS FOR THEM BE |
| | DEFERRED TO A LATER TIME. |
| | |
| | 5) THE PRODUCT APPROVAL SUBMITTALS FOR THE ROOF |
| | COVERING MATERIALS HAVE NOT BEEN REVIEWED AND APPROVED |
| | IN WRITING BY THE DESIGNER OF RECORD. FBC 107.3.4 |
| | |
| | 6) SPECIFY THE FASTENER SPACING AND NUMBER OF ROWS FOR |
| | THE PERIMETER AND CORNER AREAS BY CIRCLING THE |
| | APPROPRIATE ITEMS FROM THE TABLES IN THE PRODUCT |
| | APPROVAL FOR THE MODIFIED BITUMEN FOR THE FLAT ROOFS. |
| | FBC 905.11.3 |
| | |
| | 7) THE ENERGY COMPLIANCE FORMS SPECIFY R-30 INSULATION |
| | IN THE ATTIC OF THE FAMILY AND KITCHEN. IT APPEARS FROM |
| | THE PLAN ELEVATIONS AND CROSS SECTIONS THAT THE ENTIRE |
| | STRUCTURE HAS SINGLE ASSEMBLY ROOF/CEILING WITH NO |
| | ATTIC. PLEASE CLARIFY OR REVISE PLANS TO SHOW THE ATTIC |
| | SPACE. FBC 107.2.1 |
| | |
| | 8) THE ENERGY FORMS SPECIFY THAT THIS IS NEW |
| | CONSTRUCTION AND IT IS A RENOVATION. FBC ENERGY |
| | CONSERVATION R405 |
| | |
| | 9) THE ENERGY FORMS SPECIFY THE WALLS TYPE AS CONCRETE |
| | BLOCK WITH R-6 INSULATION AND MOST OF THEM ARE 2 X 4 |
| | WOOD FRAME. FBC ENERGY CONSERVATION R405 |
| | |
| | 10) THE ENERGY FORMS SPECIFY THAT THE COOLING FOR |
| | SYSTEM 1 IS 47.5 KBTUS. THE PLANS SPECIFY 36,500 BTUS ( |
| | 3 TON ) AND THE EQUIPMENT SIZING CALCULATIONS HAS |
| | 36,300 BTUS ( 3 TONS ). PLEASE CLARIFY THE ENERGY FORM |
| | AND THE OTHER DOCUMENTS. FBC ENERGY CONSERVATION |
| | R403.6.1.1 |
| | |
| | 11) PROVIDE EXTERIOR WALL SECTIONS FOR THE VARIOUS |
| | EXTERIOR WALL TYPES AND IN-FILL WHICH SPECIFIES THE |
| | INTERIOR / EXTERIOR WALL COVERINGS, FINISHES AND |
| | INSULATION. FBC 107.2.1 |
| | |
| | 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |