| 2017-05-02 15:28:10 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT A-02 SHOWS DEPTH OF ACCESSIBLE SHOWER AT 2'10" |
| | IT SHALL BE 3'. PER FBC ACC 608.2.1 |
| | |
| | 2. SHT A-04 SHOWER CONTROLS SHALL COMPLY WITH FBC ACC |
| | 608.5.1 TRANSFER TYPE SHOWER COMPARTMENTS. |
| | IN TRANSFER TYPE SHOWER COMPARTMENTS, THE CONTROLS, |
| | FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON |
| | THE SIDE WALL OPPOSITE THE SEAT 38 INCHES (965 MM) |
| | MINIMUM AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE |
| | SHOWER FLOOR AND SHALL BE LOCATED ON THE CONTROL WALL |
| | 15 INCHES (380 MM) MAXIMUM FROM THE CENTERLINE OF THE |
| | SEAT TOWARD THE SHOWER OPENING. PLEASE REMOVE DETAIL |
| | SHOWING 27" MAX FROM CENTER OF CONTROLS TO FRONT OF |
| | SHOWER. IT SHALL BE 15" |
| | |
| | 3. SHT. P-2 THE SANITARY RISER THE BRANCH DRAIN FOR THE |
| | LAVATORY SHALL CONNECT BETWEEN THE LAST TO WATER |
| | CLOSETS NOT THE END OF THE BRANCH. PER FBC PL 914.2 |
| | VENT CONNECTION. |
| | THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN |
| | THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL |
| | CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED |
| | IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE |
| | SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |