2017-05-02 08:57:431ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17041175
 5/2/17
  
 1) THE EXHAUST SYSTEM REQUIRES INSTALLATION OF AN
 ENERGY RECOVERY VENTILATOR- SEE SECTION & TABLE
 C403.2.6 FBC-14 ENERGY CONSERVATION. PLEASE REVISE THE
 PLAN ACCORDINGLY.
  
 2) PLEASE PROVIDE EXHAUST VENTILATION CALULATIONS FOR
 THE BAQTHROOMS AND LOCKER ROOMS- TABLE 403.3 FBC-14
 MECHANICAL.
  