| Plan Review Notes For Permit 17041175 |
| Permit Number |
17041175 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-02 08:57:43 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041175 | | | 5/2/17 | | | | | | 1) THE EXHAUST SYSTEM REQUIRES INSTALLATION OF AN | | | ENERGY RECOVERY VENTILATOR- SEE SECTION & TABLE | | | C403.2.6 FBC-14 ENERGY CONSERVATION. PLEASE REVISE THE | | | PLAN ACCORDINGLY. | | | | | | 2) PLEASE PROVIDE EXHAUST VENTILATION CALULATIONS FOR | | | THE BAQTHROOMS AND LOCKER ROOMS- TABLE 403.3 FBC-14 | | | MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|