| | C405.5 INTERIOR LIGHTING POWER REQUIREMENTS |
| | (PRESCRIPTIVE). |
| | A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL |
| | CONNECTED LIGHTING POWER CALCULATED UNDER SECTION |
| | C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER |
| | CALCULATED UNDER SECTION C405.5.2. |
| | |
| | 110.24 AVAILABLE FAULT CURRENT. (A) FIELD MARKING. |
| | SERVICE EQUIPMENT IN OTHER THAN DWELLING UNITS SHALL BE |
| | LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE |
| | FAULT CURRENT. THE FIELD MARKLNG(S) |
| | SHALL INCLUDE THE DATE THE FAULT-CURRENT CALCULATION |
| | WAS PERFORMED AND BE OF SUFFICIENT DURABILITY TO |
| | WITHSTAND THE ENVIRONMENT INVOLVED. |
| | |
| | (B) MODIFICATIONS. WHEN MODIFICATIONS TO THE ELECTRICAL |
| | INSTALLATION OCCUR THAT AFFECT THE MAXIMUM AVAILABLE |
| | FAULT CURRENT AT THE SERVICE, THE MAXIMUM AVAILABLE |
| | FAULT CURRENT |
| | SHALL BE VERIFIED OR RECALCULATED AS NECESSARY TO |
| | ENSURE THE SERVICE EQUIPMENT RATINGS ARE SUFTICIENT FOR |
| | THE MAXIMUM AVAILABLE FAULT CULTENT AT THE LINE |
| | TERMINALS OF THE EQUIPMENT. |
| | THE REQUIRED FIELD MARKING(S) IN LLO.24(A) SHALL BE |
| | ADJUSTED TO REFLECT THE NEW LEVEL OF MAXIMUM AVAILABLE |
| | FAULT CURRENT |
| | |
| | 408.4 FIELD IDENTIFICATION REQUIRED. (B) SOURCE OF |
| | SUPPLY. ALL SWITCHBOARDS,SWITEHGEAR, AND PANELBOARDS |
| | SUPPLIED BY A FEEDER(S) IN OTHER THAN ONE- OR |
| | TWO-FAMILY DWELLINGS SHALL BE |
| | MARKED TO INDICATE EACH DEVICE OR EQUIPMENT WHERE THE |
| | POWER ORIGINATES. |
| | |
| | |