| Date |
Text |
| 2017-07-19 18:59:23 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 2ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) THE HEATING AND COOLING EQUIPMENT LISTED ON THE |
| | ENERGY FORM R405-2014 DOES NOT MATCH THE EQUIPMENT |
| | SPECIFIED ON THE MECHANICAL PLANS OR THE EQUIPMENT |
| | SIZING SUMMARY FORMS. PLEASE CORRECT. FBC ENERGY |
| | CONSERVATION - SECT. R103.2 |
| | |
| | 2) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED BY THE DESIGNER OF RECORD. FBC 107.3.4 - |
| | PROVIDE TWO SETS OF PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC 61G20-3.001 PER |
| | FLORIDA STATUTE 553.842 (5) THAT HAVE BEEN REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 3) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR ENHANCED FASTENING OF THE CERTAINTEED |
| | MODIFIED BITUMEN ROOFING SYSTEM AS REQUIRED BY |
| | LIMITATION NUMBER 7 ON PAGE 42 OF NOA NO. 14-0529.02. |
| | |
| | 4) THE CASEMENT WINDOW SPECIFIED ON SHEET A-402.00 IS |
| | LARGER THAN THE MAXIMUM WINDOW SIZE ALLOWED BY NOA NO. |
| | 16-0629.21. SUBMIT ANOTHER PRODUCT APPROVAL OR REVISE |
| | THE WINDOW SIZE. FBC-R301.2.1 |
| | |
| | 5) NOA NO. 07-1105.05 FOR THE MAXIM SKYLIGHT EXPIRED ON |
| | JANUARY 10, 2013. SUBMIT A CURRENT PRODUCT APPROVAL FOR |
| | THE SKYLIGHT. FBC 107.3.4 |
| | |
| | 6) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |