| Plan Review Notes For Permit 17041082 |
| Permit Number |
17041082 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-07-18 12:45:02 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #17041082 | | | 7/18/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW SYSTEM- SECTION R403.6.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) PROVIDE AN AHRI CERTIFICATE FOR THE NEW SYSTEM- | | | SECTION R101.4.7. | | | | | | 3) AS PREVIOUSLY REQUESTED PROVIDE COMBUSTION AIR | | | CALCULATIONS AND A VENTING PLAN FOR THE GAS DRYER. | | | | | | 4) EXHAUST VENTILATION IS REQUIRED FOR THE KITCHEN PER | | | TABLE M1507.4 FBC-14 RESIDENTIAL. PLEASE INDICATE IF A | | | NEW EXHAUST HOOD AND DUCT WILL BE INSTALLED AND PROVIDE | | | DETAILS ON THE PLANS. | | | | | | 5) PROVIDE A MEANS OF RETURN AIR FROM BEDROOM #2 TO THE | | | AIR HANDLER- SECTION M1602.4. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|