| Notes |
| Date |
Text |
| 2017-05-10 17:22:59 | 1ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL | | | PERMIT #17041082 | | | 5/10/17 | | | | | | 1) NO MECHANICAL PLANS OR SPECIFICATIONS HAVE BEEN | | | SUBMITTED. IN ORDER TO DO A COMPREHENSIVE REVIEW PLEASE | | | PROVIDE THE FOLLOWING: | | | | | | A) AC DUCT LAYOUT PLAN | | | B) AC EQUIPMENT SCHEDULE | | | C) KITCHEN AND BATH EXHAUST PLANS | | | D) COMBUSTION AIR CALCULATIONS, AND VENTING DETAILS FOR | | | THE GAS DRYER | | | E) ENGINEERING FOR TIE DOWN OF THE AC CONDENSER. | | | F) CONDENSATE DISPOSAL DETAILS FOR THE AHU. | | | G) MANUFACTURER'S SPECIFICATIONS FOR THE WATER HEATER, | | | THE RANGE, AND THE RANGE HOOD. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|