Plan Review Notes
Plan Review Notes For Permit 17041082
Permit Number 17041082
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-10 17:22:591ST REVIEW FBC-2014 RESIDENTIAL MECHANICAL
 PERMIT #17041082
 5/10/17
  
 1) NO MECHANICAL PLANS OR SPECIFICATIONS HAVE BEEN
 SUBMITTED. IN ORDER TO DO A COMPREHENSIVE REVIEW PLEASE
 PROVIDE THE FOLLOWING:
  
 A) AC DUCT LAYOUT PLAN
 B) AC EQUIPMENT SCHEDULE
 C) KITCHEN AND BATH EXHAUST PLANS
 D) COMBUSTION AIR CALCULATIONS, AND VENTING DETAILS FOR
 THE GAS DRYER
 E) ENGINEERING FOR TIE DOWN OF THE AC CONDENSER.
 F) CONDENSATE DISPOSAL DETAILS FOR THE AHU.
 G) MANUFACTURER'S SPECIFICATIONS FOR THE WATER HEATER,
 THE RANGE, AND THE RANGE HOOD.
  