| Plan Review Notes For Permit 17041058 |
| Permit Number |
17041058 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-07 09:13:08 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS: | | | | | | 1. PROVIDE ELECTRICAL PLAN FOR REVIEW. ELECTRICAL PLAN | | | REQUIRED TO BE SIGNED BY ELECTRICAL QUALIFIER OR DESIGN | | | PROFESSIONAL. FBC 107.3.5, FS 471.003(2)(H), 471.025 | | | 2. PROVIDE FLOOR PLAN INDICATING LOCATION OF REQUIRED | | | SMOKE ALARMS. IF NONE ARE EXISTING, OR NOT TO CODE, | | | SHOW AS NEW INSTALLATION. FBC 907.2.11 | | | 3. PROVIDE LOCATION ON PLAN OF ALL OUTLETS IN KITCHEN | | | PER CODE. SHOW AS EXISTING OR NEW AS REQUIRED. NEC | | | 210.52 | | | 4. PROVIDE PANEL SCHEDULE, INDICATE ANY NEW OR ALTERED | | | CIRCUITS, AFCI OR GFCI PROTECTION WHERE APPLICABLE. NEC | | | 408.4, 210.8, 210.12(B) | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|