| 2017-05-04 12:18:16 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17041051 |
| | W. P. B. PERMIT: 16080044 |
| | ADD: 324 DATURA ST./ 1ST FLOOR LOBBY |
| | CONT: GERALD CONTRACTING |
| | TEL: 561-832-9785 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MAY 04/2017 |
| | ACTION: DENIED |
| | |
| | THE REVISION OF THE 1ST FLOOR LOBBY AND ATRIUM AREA |
| | SHOWS THE WON DOOR BEING REMOVED AND BI-SWING GLAZED |
| | DOORS AND SIDE LIGHT BEING INSTALLED. THE 2014 FBC-B |
| | SECTION 404.6 DESCRIBES THE REQUIREMENTS FOR 1 HOUR |
| | FIRE BARRIERS, GLASS WALL PANELS AND THE DOORS HAVING |
| | TO COMPLY WITH FBC-B TABLE 716.5. |
| | |
| | THE FLOOR PLAN A-1.0 SHOWS THE NEW DOORS IDENTIFIED AS |
| | ?B?. THE DOOR SCHEDULE FOR TYPE B ILLUSTRATIONS B1 AND |
| | B2 BOTH SHOW SOLID CORE DOORS, NO GLAZING. TABLE 716.5 |
| | FOR OTHER FIRE BARRIER (NOTE LISTED UNDER FIRE BARRIERS |
| | AS SHAFTS, EXIT ACCESS STAIRWAYS) REQUIRES ? HOUR |
| | ASSEMBLY , VISION PANEL MAXIMUM SIZE TESTED AND THE |
| | VISION PANEL GLAZING MARKED WITH D-H-NT-45 AND |
| | SIDELIGHT WITH THE SAME MARKINGS. |
| | |
| | THE OTHER ISSUES WITH THE SIDE LIGHT WOULD BE FOUND |
| | UNDER 404.6 EXCEPTIONS ; |
| | |
| | 1. A FIRE BARRIER IS NOT REQUIRED WHERE A GLASS WALL |
| | FORMING A SMOKE PARTITION IS PROVIDED. THE GLASS WALL |
| | SHALL COMPLY WITH ALL OF THE FOLLOWING: |
| | |
| | 1.1. AUTOMATIC SPRINKLERS ARE PROVIDED ALONG BOTH SIDES |
| | OF THE SEPARATION WALL AND DOORS, OR ON THE ROOM SIDE |
| | ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM SIDE. THE |
| | SPRINKLERS SHALL BE LOCATED BETWEEN 4 INCHES AND 12 |
| | INCHES (102 MM AND 305 MM) AWAY FROM THE GLASS AND AT |
| | INTERVALS ALONG THE GLASS NOT GREATER THAN 6 FEET (1829 |
| | MM). THE SPRINKLER SYSTEM SHALL BE DESIGNED SO THAT THE |
| | ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF |
| | THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION; |
| | |
| | 1.2. THE GLASS WALL SHALL BE INSTALLED IN A GASKETED |
| | FRAME IN A MANNER THAT THE FRAMING SYSTEM DEFLECTS |
| | WITHOUT BREAKING (LOADING) THE GLASS BEFORE THE |
| | SPRINKLER SYSTEM OPERATES; AND |
| | |
| | 1.3. WHERE GLASS DOORS ARE PROVIDED IN THE GLASS WALL, |
| | THEY SHALL BE EITHER SELF-CLOSING OR AUTOMATIC-CLOSING. |
| | |
| | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. |
| | WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |