Plan Review Notes
Plan Review Notes For Permit 17041024
Permit Number 17041024
Review Stop E
Sequence Number 1
Notes
Date Text
2017-05-12 13:23:52JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 CABANA WILL NEED A SEPARATE MEANS OF DISCONNECT AND A
 GROUNDING SYSTEM AT THE CABANA BUILDING.
 SUBMIT A RISER DIAGRAM AND PANEL SCHEDULE FOR THE
 CIRCUITS IN THE CABANA.
 SEE 225.30, 225.39, 250.32