| Plan Review Notes For Permit 17041008 |
| Permit Number |
17041008 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-24 18:30:08 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ONE STORY STRUCTURE HAS A 6:12 SLOPED ROOF AND | | | IS LOCATED IN EXPOSURE CATEGORY C WITH A 170 MPH VULT | | | WINDSPEED. THE PRODUCT APPROVAL FOR THE TRI-BUILT SELF | | | ADHERED UNDERLAYMENT SPECIFIES THE MAXIMUM DESIGN | | | PRESSURE OF -60.0 PSF FOR A MIN. 19/32 " PLYWOOD DECK. | | | THIS IS NOT ADEQUATE FOR THE CORNER AREAS OF THE ROOF. | | | FBC-R 301.2.1 | | | |
|