| Notes |
| Date |
Text |
| 2017-04-24 19:04:06 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE ROOF ASSEMBLY THAT IS LISTED IN THE PRODUCT | | | APPROVAL FOR SYSTEM W-4 HAS TO BE INSTALLED AS | | | SPECIFIED. THE FLINTLASTIC SA NAILBASE IS NOT OPTIONAL | | | AND IS REQUIRED TO BE USED FOR THIS SYSTEM. ALL OF THE | | | SYSTEMS IN THIS PRODUCT APPROVAL REQUIRE MECHANICALLY | | | FASTENED BASE SHEETS. FBC-R301.2.1 | | | | | | 2) YOU ARE REQUIRED TO CIRCLE THE APPROPRIATE EXPOSURE, | | | ENCLOSURE, ROOF HEIGHT ZONES AND NAIL SPACING UNDER THE | | | 170 MPH WIND SPEED. FBC 107.2.1 |
|