| Notes |
| Date |
Text |
| 2017-04-27 09:51:11 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040981 | | | 4/27/16 | | | | | | 1) SHEETS MP-1, SUITE 310: KEYED NOTE #2 WHICH | | | DESIGNATES AN EXHAUST FAN IS SHOWN AT THE FAN COIL | | | LOCATIONS IN THE BEDROOMS. PLEASE CORRECT, AND REVISE | | | KEYED NOTE #3 WHICH IS REFERENCING A FAN COIL UNIT | | | UNDER KEYED NOTE #2. | | | | | | 2) MP-4 & MP-5: REVISE KEYED NOTE #3 WHICH IS | | | REFERENCING A FAN COIL UNIT UNDER KEYED NOTE #2 NEEDS | | | TO BE REVISED. | | | | | | 3) PROVIDE AC CHANGE OUT FORMS AND AHRI CERTIFICATES | | | FOR ALL FAN COIL UNITS BEING REPLACED. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|