| Date |
Text |
| 2017-05-09 11:46:50 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17040981 |
| | ADD: 901 S. FLAGLER DR. DORMS: 307, 310, 311, 312, 407, |
| | 410, 411, 412, 507, & 508 |
| | CONT: BMS CATS INC. |
| | TEL: 954-319-3524 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SAT. MAY 06/2017 |
| | ACTION: DENIED |
| | |
| | 1A) ALL OF THE 10 DORM UNITS SHOW EITHER A NOTE # 2 OR |
| | 5 FOR A NEW EXTERIOR DOOR AND SIDE LIGHT (NOTE # 2) OR |
| | A NEW EXTERIOR DOOR W/ TRANSOM (NOTE # 5). PRODUCT |
| | APPROVAL: FL -14676.1. PLEASE SUBMIT THE PRODUCT |
| | APPROVAL IN COMPLIANCE WITH; |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS, SIDELIGHTS & TRANSOMS |
| | |
| | 1B) THE EXTERIOR DOOR NOTES 2 & 5 BOTH HAVE THE WORDING |
| | DAYBAR PRODUCT APPROVAL FL-14676.1 OR EQUAL. |
| | THE PLANS CANNOT SAY EQUAL. INFORMATIONAL/ EQUIVALENCY |
| | 2014 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2.1.3: W.P.B. |
| | ADMINISTRATIVE CODE/2014 DRAWINGS & SPECIFICATIONS |
| | SHALL CONTAIN INFORMATION, IN THE FORM OF NOTES OR |
| | OTHERWISE, AS TO THE QUALITY OF MATERIALS, WHERE |
| | QUALITY IS ESSENTIAL TO CONFORMITY WITH THE TECHNICAL |
| | CODES. SUCH INFORMATION SHALL BE SPECIFIC TO THE |
| | TECHNICAL CODES "SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART, NOR THE TERM "LEGAL" OR ITS EQUIVALENT BE USED AS |
| | A SUBSTITUTE FOR SPECIFIC INFORMATION". |
| | |
| | 1C) IDENTIFY GLAZING. FOR ALL PRODUCTS WITH GLAZING, |
| | PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF |
| | GLAZING, MULLION INFORMATION IF REQUIRED, ATTACHMENTS |
| | AND ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 2014 |
| | FBC-B 1405.13.1 INSTALLATION. WINDOWS AND DOORS SHALL |
| | BE INSTALLED IN ACCORDANCE WITH APPROVED MANUFACTURER?S |
| | INSTRUCTIONS. FASTENER SIZE AND SPACING SHALL BE |
| | PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE CALCULATED |
| | BASED ON MAXIMUM LOADS AND SPACING USED IN THE TESTS. |
| | |
| | 2) THERE ARE UNITS WHERE THE BATHROOM FLOORING TILE IS |
| | BEING REMOVED, 9 OF THE 10 DORMS, 310, 311, 312, 407, |
| | 410, 411, 412, 507 & 508. PLEASE SHOW COMPLIANCE WITH: |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 2A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 2B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 3) FOR ALL OF THE UNITS DEMOLITION NOTE # 1 INDICATES |
| | THE REMOVAL OF THE DRYWALL AND INSULATION ON ALL OF THE |
| | EXTERIOR WALLS. THERE ARE ALSO NOTES FOR NEW TRANE FAN |
| | COIL UNITS. IN THIS SUBMISSION THERE HAS BEEN NO |
| | DOCUMENTATION TO THE 2014 ENERGY CODE. |
| | C401.2 APPLICATION. COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH ONE OF THE FOLLOWING: |
| | 3.1. THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1. |
| | 3.2. THE REQUIREMENTS OF SECTIONS C402, C403, C404 AND |
| | C405. IN ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY |
| | WITH EITHER SECTION C406.2, C406.3 OR C406.4. |
| | 3.3. THE REQUIREMENTS OF SECTION C407, C402.4, C403.2, |
| | C404, C405.2, C405.3, C405.4, C405.6 AND C405.7. THE |
| | BUILDING ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 |
| | PERCENT OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | |
| | 4) SHEET A-5 SHOWS THIS DORMITORY AS THE ACCESSIBLE |
| | UNIT. THE DESIGNER OF RECORD SHOWS ON THE PLANS THE USE |
| | OF AN ELECTRONIC DOOR OPENER TO GAIN ACCESS INTO THE |
| | ACCESSIBLE DORM. THE QUESTION IS HOW TO MAKE THE |
| | BATHROOM A FULLY ACCESSIBLE BATHROOM AND OR STALL? THE |
| | PLANS SHOW A CODE COMPLIANT SHOW A COMPLIANT TRANSFER |
| | SHOWER, LAVATORY AND MIRROR BUT NOT WATER CLOSET. 604.8 |
| | ACCESS. CODE FBC 2014. |
| | |
| | 5) PLEASE PROVIDE WHERE CODE COMPLIANCE CAN BE FOUND |
| | FOR THE 2014 FBC-ACCESS. CODE ) FBC-ACCESS. CODE 224.4 |
| | GUEST ROOMS WITH COMMUNICATION FEATURES. IN TRANSIENT |
| | LODGING FACILITIES, GUEST ROOMS WITH COMMUNICATION |
| | FEATURES COMPLYING WITH 806.3 SHALL BE PROVIDED IN |
| | ACCORDANCE WITH TABLE 224.4. |
| | |
| | 6) ) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | E-MAIL: [email protected] |
| | |