2017-05-03 09:55:44PROVISO:
  
 FIRE HYDRANTS APPROVED FOR USE:
 HYDRANTS SHALL CONFORM TO REQUIREMENTS OF AWWA STANDARD
 C502-94 FOR DRY BARREL HYDRANTS OR THE LATEST REVISION,
 AS TO THE DESIGN, COMPONENT MATERIALS, CONSTRUCTION AND
 MANUFACTURE EXCEPT AS MODIFIED OR NOTED IN THE CITY
 TECHNICAL SPECIFICATIONS
  
 APPROVED HYDRANTS WILL BE USED IN THE CONSTRUCTION OF
 SYSTEMS TO BE OWNED OR OPERATED BY THE CITY OF WEST
 PALM BEACH. APPROVED HYDRANTS SHALL BE USED IN THE
 CONSTRUCTION OF PRIVATE SYSTEMS WITHIN THE CORPORATE
 BOUNDARIES OF THE CITY OF WEST PALM BEACH.
  
 ACCEPTED HYDRANTS: CLOW AMERICAN, MEDALLION B-84-B,
 MUELLER SUPER CENTURION 250 OR KENNDY GUARDIAN.
  
 HYDRANT COATINGS:
 WHEN CONSTRUCTED TO THE CITY OF WEST PALM BEACH
 TECHNICAL SPECIFICATIONS, HYDRANTS SHALL HAVE A SHOP
 COAT OF SILVER PAINT APPLIED AT THE MANUFACTURER.
 CONTRACTORS SHALL PAINT THE HYDRANT BONNETS WITH THE
 FOLLOWING COATING AFTER INSTALLATION AND PRIOR TO
 ACCEPTANCE. CONTRACTORS SHALL CLEAN, PREP, AND PAINT
 ALL DAMAGED FACTORY PAINT.
  
 PAINT FOR FIRE HYDRANT BONNET (REQUIRED)
 HENTZEN COATING, INC.: ALERT SERIES LIGHT REFLECTIVE
 COATING
 PAINT FOR THE BARREL SECTION AND NOZZLE CAPS (TOUCH-UP
 PAINT)
 SHERWIN-WILLIAMS: SILVER-BRITE ALUMINUM PAINT. SALE
 IDENTIFICATION NO. B59S11
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116