| 2017-04-25 16:09:31 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040955 | | | 4/25/17 | | | | | | 1) THE REVISED PLAN SHOWS DUCTWORK FROM AHU'S #9 & 11 | | | PENETRATING INTO THE INTERIOR EXIT STAIRWAYS WHICH IS | | | PROHIBITED PER SECTION 1022.6 FBC-14 BUILDING. THE | | | ORIGINAL PLAN SHOWED INDEPENDENT SYSTEMS #16 & 17 | | | OPERATING IN THE STAIRWAYS WHICH HAVE NOW BEEN | | | ELIMINATED- PLEASE CORRECT. | | | | | | 2) THE REVISED PLAN SHOWS A NEW SPLIT SYSTEM WHICH IS | | | ALSO LABELED #18 LIKE THE EXISTING HEAT PUMP AHU. | | | PLEASE SHOW THE LOCATION OF THE NEW SYSTEM AND PROVIDE | | | AC COOLING AND HEATING CALCULATIONS IN COMPLIANCE WITH | | | SECTION C403.2.1 FBC-14 ENERGY CONSERVATION. | | | | | | 3) REVISE THE ENERGY CALCULATIONS TO INCORPORATE THE | | | CHANGES TO THE APPROVED AC SYSTEMS. | | | | | | 4) PROVIDE A NARRATIVE FRROM THE DESIGN PROFESSIONAL | | | ITEMIZING ALL CHANGES TO THE APPROVED MECHANICAL PLANS, | | | AND ALL CORRECTIONS MADE TO THE NEW REVISED PLANS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|