Plan Review Notes
Plan Review Notes For Permit 17040923
Permit Number 17040923
Review Stop E
Sequence Number 1
Notes
Date Text
2017-05-03 10:10:55PLEASE ADDRESS MECH. COMMENTS AND PROVIDE A REVISED
 LOAD CALCULATION OF THE ELECTRICAL SERVICE AS THIS IS A
 SIGNIFICANT LOAD BEING ADDED TO EXISTING SERVICE. ALSO
 A RECEPTACLE FOR SERVICE MUST BE INSTALLED AT THE
 CONDENSOR LOCATION IF ONE IS NOT EXISTING. FBC 107.3.5
  
 V. PEREZ
 *6717