2017-06-20 09:21:54CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS (3RD REVIEW):
  
 PREVIOUS COMMENTS NOT ADDRESSED SATISFACTORILY:
  
 1. NO LIGHTING CONTROL SPECIFIED FOR WAITING ROOM AND
 RECEPTION AREA. C405.2 (PREVIOUS COMMENT #3)
 2. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY
 FBC C401.2 AND ASHREA 90.1: 8.4.2 (PREVIOUS COMMENT #4)
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  