| Plan Review Notes For Permit 17040913 |
| Permit Number |
17040913 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-06-20 09:21:54 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | | | | | ELECTRICAL REVIEW COMMENTS (3RD REVIEW): | | | | | | PREVIOUS COMMENTS NOT ADDRESSED SATISFACTORILY: | | | | | | 1. NO LIGHTING CONTROL SPECIFIED FOR WAITING ROOM AND | | | RECEPTION AREA. C405.2 (PREVIOUS COMMENT #3) | | | 2. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY | | | FBC C401.2 AND ASHREA 90.1: 8.4.2 (PREVIOUS COMMENT #4) | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | | | | SINCERELY, | | | | | | JOHN PEARSON | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6746 | | | [email protected] | | | |
|