| 2017-06-05 10:50:18 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. INDICATE ON PLAN WHICH AREAS WILL BE WIRED PER THE |
| | REQUIREMENTS FOR HEALTH CARE FACILITIES. NEC 517.13 |
| | 2. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE WIRED |
| | TO THE NORMAL LIGHTING BRANCH CIRCUIT IN THE SAME AREA. |
| | PROVIDE CORRECTION. NEC 700.12(F) |
| | 3. SHEET E-1, THERE IS A NOTE THAT STATES THE LIGHTING |
| | WILL BE PROVIDED WITH OCCUPANCY SENSORS, HOWEVER, THE |
| | PLAN SHOWS NORMAL SWITCHING. CLARIFY AND/OR CORRECT. |
| | FBC 107.2.1, FBC C405.2 |
| | 4. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY |
| | FBC C401.2 AND ASHREA 8.4.2. |
| | 5. NOTE 14, SHEET E-1, STATES THAT ALL RECEPTACLES |
| | SHALL BE TAMPER-RESISTANT PER NEC 406.11. SECTION |
| | 406.11 IS THE CODE REQUIREMENT FOR RECEPTACLE |
| | GROUNDING. ARE YOU REFERRING TO NEC 406.14 IN REFERENCE |
| | TO CHILD CARE FACILITIES? PLEASE CLARIFY AND/OR |
| | CORRECT. FBC 107.2.1, NEC 406.14 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |