2017-06-05 10:50:18CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. INDICATE ON PLAN WHICH AREAS WILL BE WIRED PER THE
 REQUIREMENTS FOR HEALTH CARE FACILITIES. NEC 517.13
 2. EMERGENCY AND EXIT LIGHTS ARE REQUIRED TO BE WIRED
 TO THE NORMAL LIGHTING BRANCH CIRCUIT IN THE SAME AREA.
 PROVIDE CORRECTION. NEC 700.12(F)
 3. SHEET E-1, THERE IS A NOTE THAT STATES THE LIGHTING
 WILL BE PROVIDED WITH OCCUPANCY SENSORS, HOWEVER, THE
 PLAN SHOWS NORMAL SWITCHING. CLARIFY AND/OR CORRECT.
 FBC 107.2.1, FBC C405.2
 4. PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY
 FBC C401.2 AND ASHREA 8.4.2.
 5. NOTE 14, SHEET E-1, STATES THAT ALL RECEPTACLES
 SHALL BE TAMPER-RESISTANT PER NEC 406.11. SECTION
 406.11 IS THE CODE REQUIREMENT FOR RECEPTACLE
 GROUNDING. ARE YOU REFERRING TO NEC 406.14 IN REFERENCE
 TO CHILD CARE FACILITIES? PLEASE CLARIFY AND/OR
 CORRECT. FBC 107.2.1, NEC 406.14
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  