| 2017-05-17 16:40:45 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW KNEE AND TOE CLEARANCE FOR LAVATORY. PER FBC |
| | ACC 606.2 |
| | |
| | 2. GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL |
| | POSITION, 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 |
| | MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP |
| | OF THE GRIPPING SURFACE. PER FBC ACC 609.4 |
| | |
| | 3. ROOM 28 P-TLT THE TOP FOR THE LAVATORY CAN NOT |
| | ENCROACH INTO THE CLEAR FLOOR SPACE OF THE TOILET. PER |
| | FBC ACC 604.3.1, 604.3.2, |
| | |
| | 4. SHT. P0.1 DETAIL P1 A VACUUM RELIEF VALVE IS |
| | REQUIRED ON A BOTTOM FED WATER HEATER .PER FBC PL 504.2 |
| | |
| | 5. THE BREAKROOM SINK, THE SINK IN THE WAITING ROOM AND |
| | A MIN OF ONE SINK IN ONE OF THE EXAM ROOMS SHALL COMPLY |
| | WITH FBC ACC 606, 212.3 SINKS. |
| | WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO |
| | FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| | ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606. |
| | |
| | 6. THE WATER FOUNTAIN SHALL COMPLY WITH FBC ACC 602. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |