2017-04-24 16:54:201ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040840
 4/24/17
  
 1) THE CITY OF WPB CONSTRUCTION SERVICES DIVISION
 REQUIRES SEPARATE PERMITS FOR ANY ALTERATIONS TO THE
 EXISTING KITCHEN HOOD OR FIRE SUPPRESSION SYSTEM AS A
 RESULT OF THE NEW ROTISSERIE INSTALLATION.
  
 2) THE CITY OF WPB CSD REQUIRES A SEPARATE PERMIT FOR
 REFRIGERATION WORK. PLEASE PROVIDE A COMPLETE SET OF
 PLANS AND SUBMITTALS UNDER SEPARATE PERMIT.
  
 3) M1: PLEASE CLARIFY THE PURPOSE OF THE EXHAUST FAN IN
 THE PHARMACY AND PROVIDE A SIZING CALCULATION.
  
 4) M2: THERE IS A LARGE AIR DEVICE SCHEDULE ON THE PLAN
 HOWEVER NO LAYOUT PLAN TO SHOW THE LOCATIONS OF THE NEW
 DEVICES- PLEASE CLARIFY.
  