| 2017-05-05 07:23:25 | 2014 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17040840 |
| | ADD: 6901 OKEECHOBEE BLVD. |
| | CONT: CORPORATE PROPERTY SERVICES INC. |
| | TEL: 954-426-5144 / JAY BOSWELL |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. MAY 04/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) THE COVER SHEET INDICATES THERE ARE 2 SHEETS WITHIN |
| | THIS DOCUMENT FOR RACK STORAGE AND ATTACHED TO THE |
| | PLANS ARE STRUCTURAL FIXTURE ANCHORAGE CALCULATIONS. |
| | THE CONTRACTOR CAN ELECT TO LEAVE THESE ITEMS WITHIN |
| | THE SET OF PLANS OR REMOVE THEM. RACK STORAGE DOES |
| | REQUIRE A SEPARATE PERMIT. IF THE RACK STORAGE |
| | DOCUMENTS ARE LEFT IN THE SET OF PLANS A NEW PLAN |
| | REVIEW STOP ( R ) FOR RACK STORAGE WILL BE ADDED. THE |
| | CONTRACTOR WILL NEED TO SUBMIT A PERMIT APPLICATION FOR |
| | THE RACK STORAGE AND THE CITY WILL ENTER IT AS A MISC. |
| | BUILDING PERMIT. THIS WILL BE AN ADDITIONAL FEE OF |
| | $80.00 AS AN ADMINISTRATIVE FEE INCLUDE THE MASTER |
| | PERMIT NUMBER ON THE FIXTURE ONLY PERMIT. |
| | |
| | 2A) SHEET D1 HAS A NOTE ON THE REMOVAL OF THE FRONT |
| | ENTRY DOORS. PLEASE PROVIDE PRODUCT APPROVAL FOR THE |
| | NEW DOORS. |
| | 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS & ROOF HATCHES. |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 2B) IDENTIFY GLAZING/ MULLIONS. FOR ALL PRODUCTS WITH |
| | GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE. 2014 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND |
| | DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED |
| | MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING |
| | SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE |
| | CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN |
| | THE TESTS. |
| | |
| | 2C) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 3) SHEET D1 HAS A NOTE FOR THE REMOVAL OF THE FRONT |
| | ENTRY DOORS, SHEET A1 IDENTIFIES THE FRONT DOOR |
| | LOCATION AS NUMBER 115 DOOR. THE DOOR SCHEDULE |
| | IDENTIFIES THE DOORS AS TYPE A, OR AUTOMATIC SLIDING |
| | DOORS SO-SX-SX-SO. SHOW COMPLIANCE WITH SECTION |
| | 1008.1.10 PANIC AND FIRE EXIT HARDWARE. |
| | |
| | 1008.1.10 PANIC AND FIRE EXIT HARDWARE. DOORS SERVING A |
| | GROUP H OCCUPANCY AND DOORS SERVING ROOMS OR SPACES |
| | WITH AN OCCUPANT LOAD OF 50 OR MORE IN A GROUP A OR E |
| | OCCUPANCY SHALL NOT BE PROVIDED WITH A LATCH OR LOCK |
| | UNLESS IT IS PANIC HARDWARE OR FIRE EXIT HARDWARE. |
| | |
| | 4) PLEASE PROVIDE THE WIND DESIGN CRITERIA FOR THIS |
| | PROJECT, PLEASE PROVIDE THE PRESSURES IN VASD SINCE THE |
| | PRODUCT APPROVALS ARE IN VASD. 2014 FBC-B 1603.1.4 WIND |
| | DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 4.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 4.2. RISK CATEGORY. |
| | |
| | 4.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 4.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 4.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |