| Plan Review Notes For Permit 17040825 |
| Permit Number |
17040825 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-21 16:40:51 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040825 | | | 4/21/17 | | | | | | 1) EXHAUST VENTILATION AT A RATE 100 CFMS PER SQ. FT. | | | IS REQUIRED FOR THE KITCHEN IF USING A VENT HOOD | | | INTERMITTENTLY- TABLE 403.3. PLEASE PROVIDE AN | | | EQUIPMENT SCHEDULE ON THE PLAN THAT SHOWS THE MAKE AND | | | MODEL AND VENTING CAPACITY OF THE HOOD, AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS. REFER TO SECTION 505.2- | | | MAKEUP AIR MAY BE REQUIRED. | | | | | | 2) INDICATE THE TYPE AND SIZE OF EXHAUST DUCT, SHOW THE | | | DUCT RUN AND TERMINATION LOCATION. | | | | | | 3) PROVIDE A SCOPE OF WORK FOR AC ALTERATIONS ON THE | | | PLAN WITH CORRELATING DRAWINGS AND DETAILS (IF | | | APPLICABLE TO THE PROJECT). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|