Plan Review Notes
Plan Review Notes For Permit 17040820
Permit Number 17040820
Review Stop E
Sequence Number 1
Notes
Date Text
2017-04-25 11:49:19JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 BN1165, BU1753, PX163
 561-805-6713
  
  
 C405.2.1.1 INTERIOR LIGHTING CONTROLS.
 EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING
 PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL
 FOR THE LIGHTING SERVING THAT AREA. THE REQUIRED
 CONTROLS SHALL BE LOCATED WITHIN THE AREA SERVED
 BY THE CONTROLS OR BE A REMOTE SWITCH THAT IDENTIFIES
 THE LIGHTS SERVED AND INDICATES THEIR STATUS.
  
 C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER.
 THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS)
 SHALL BE THE SUM OF THE WATTS OF ALL INTERIOR
 LIGHTING EQUIPMENT AS DETERMINED IN ACCORDANCE WITH
 SECTIONS C405.5.1.1 THROUGH C405.5.1.4.
  
 FAULT CURRENT CALCULATION REQUIRED BY 110.24
  
 SUBMIT THE INFORMATION SHOWING LIGHTING CONTROL,
 DENSITY LIGHTING CACULATION, AND FAULT CURRENT
 BEFORE THE ELECTRICAL FINAL FOR REVIEW.
  
  
  