| Plan Review Notes For Permit 17040820 |
| Permit Number |
17040820 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-25 11:49:19 | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | BN1165, BU1753, PX163 | | | 561-805-6713 | | | | | | | | | C405.2.1.1 INTERIOR LIGHTING CONTROLS. | | | EACH AREA ENCLOSED BY WALLS OR FLOOR-TO-CEILING | | | PARTITIONS SHALL HAVE AT LEAST ONE MANUAL CONTROL | | | FOR THE LIGHTING SERVING THAT AREA. THE REQUIRED | | | CONTROLS SHALL BE LOCATED WITHIN THE AREA SERVED | | | BY THE CONTROLS OR BE A REMOTE SWITCH THAT IDENTIFIES | | | THE LIGHTS SERVED AND INDICATES THEIR STATUS. | | | | | | C405.5.1 TOTAL CONNECTED INTERIOR LIGHTING POWER. | | | THE TOTAL CONNECTED INTERIOR LIGHTING POWER (WATTS) | | | SHALL BE THE SUM OF THE WATTS OF ALL INTERIOR | | | LIGHTING EQUIPMENT AS DETERMINED IN ACCORDANCE WITH | | | SECTIONS C405.5.1.1 THROUGH C405.5.1.4. | | | | | | FAULT CURRENT CALCULATION REQUIRED BY 110.24 | | | | | | SUBMIT THE INFORMATION SHOWING LIGHTING CONTROL, | | | DENSITY LIGHTING CACULATION, AND FAULT CURRENT | | | BEFORE THE ELECTRICAL FINAL FOR REVIEW. | | | | | | | | | |
|