| 2017-04-26 17:34:13 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. PLANS APPEAR TO BE PRINTED HALF SIZE. SEE SHEET A2, |
| | SCALE IS 1/4", BUT THIS DOES NOT CORRELATE WITH THE |
| | PLAN. FBC 107, PLANS TO BE LEGIBLE FOR PLAN REVIEW, |
| | INSPECTIONS, RECORD RETENTION. PRINT FULL SIZE PLANS |
| | FOR REVIEW. |
| | |
| | 2. THE ENGINEER'S TITLE BLOCK LACKS THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER REQUIRED FOR FLORIDA INTERNATIONAL |
| | ENGINEERING & TESTING LAB. REVISE TO INCLUDE, FS471, |
| | FAC61G15-23.002. |
| | |
| | 3. SHEET A1 STATES THAT THIS SPACE IS 182 SQUARE FEET, |
| | REVISE AS THE SPACE APPEARS LARGER. |
| | |
| | 4. SHEET A0 STATES THAT THIS IS A LEVEL 2 ALTERATION. |
| | IS THIS ALSO A CHANGE OF OCCUPANCY? |
| | |
| | 5. THE PARKING LOT DOES NOT COMPLY WITH THE FLORIDA |
| | BUILDING CODE OR ADA. THE ACCESSIBLE PARKING SPACE IS |
| | NOT LOCATED ON THE CLOSEST ROUTE. SUBMIT A PERMIT |
| | APPLICATION TO BRING THE PARKING LOT INTO COMPLIANCE. |
| | IT APPEARS THAT THE PARKING LOT WAS RESTRIPED SOME TIME |
| | BETWEEN 2009 AND 2011 WITHOUT A PERMIT. |
| | |
| | 6. PAPA RECORDS SHOW THREE SUITE NUMBERS FOR THIS |
| | LOCATION. DOES APPLICANT PREFER SEPARATE ADDRESSES? |
| | THIS MAY BE POSSIBLE, PLEASE ADVISE. |
| | |
| | THE APPLICATION IS FOR SUITE 102, BUT IF SUBWAY IS |
| | #101, SHOULDN'T THIS UNIT BE #103? PREVIOUS PERMITS |
| | SHOW THAT SUITE #102 IS IN THE CENTER; IT IS NOT CLEAR |
| | WHY THE APPLICATION IS FOR SUITE 102. |
| | |
| | 7. PROVIDE TOTAL SQUARE FOOT AREA FOR THIS SPACE, FBC |
| | CHAPTER 10. LS1 SHOWS AN OCCUANT LOAD OF 4 FOR AN |
| | OFFICE, BUT NO OFFICE IS SHOWN ON THE PLAN. REVISE TO |
| | CLARIFY. |
| | |
| | 8. REVISE PLAN TO PROVIDE INFORMATION ABOUT THE |
| | STOCKROOM AND THE STORAGE AREAS; WHAT WILL BE STORED IN |
| | THESE SPACES? FBC 107. |
| | |
| | 9. A LOBBY IS SHOWN, BUT PLAN STATES THIS IS |
| | MERCANTILE. WHERE IS THE STORE? ONLY A LOBBY, SERVICES |
| | AREA, STOCKROOM AND STORAGE ARE SHOWN, FBC 107. |
| | |
| | 10. REVISE PLAN TO CLARIFY WHAT THE PURPOSE IS OF THE |
| | "SERVICE AREA". IF THIS IS A CHECK OUT COUNTER, REVISE |
| | PLAN TO INCLUDE DETAILS TO SHOW COMPLIANCE WITH FBC A |
| | 904, CHECK OUT AISLES AND SALES AND SERVICE COUNTERS. |
| | |
| | 11. THE UNNUMBERED SWING DOOR LACKS THE MANEUVERING |
| | CLEARANCE REQUIRED BY FBC A 404.2.4, SEE FIGURE |
| | 404.2.4.1(A). |
| | |
| | 12. REVISE PLAN TO SHOW DETAILS FOR THE ENTRANCE TO |
| | SHOW COMPLIANCE WITH FBC A 303. |
| | |
| | 13. PLAN INCLUDES A DESCRIPTIVE NOTE ON EACH SHEET THAT |
| | STATES "BUILDING REPAIRS"; WHAT WILL BE REPAIRED? FBC |
| | 107. |
| | |
| | |