Plan Review Notes
Plan Review Notes For Permit 17040820
Permit Number 17040820
Review Stop B
Sequence Number 1
Notes
Date Text
2017-04-26 17:34:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PLANS APPEAR TO BE PRINTED HALF SIZE. SEE SHEET A2,
 SCALE IS 1/4", BUT THIS DOES NOT CORRELATE WITH THE
 PLAN. FBC 107, PLANS TO BE LEGIBLE FOR PLAN REVIEW,
 INSPECTIONS, RECORD RETENTION. PRINT FULL SIZE PLANS
 FOR REVIEW.
  
 2. THE ENGINEER'S TITLE BLOCK LACKS THE CERTIFICATE OF
 AUTHORIZATION NUMBER REQUIRED FOR FLORIDA INTERNATIONAL
 ENGINEERING & TESTING LAB. REVISE TO INCLUDE, FS471,
 FAC61G15-23.002.
  
 3. SHEET A1 STATES THAT THIS SPACE IS 182 SQUARE FEET,
 REVISE AS THE SPACE APPEARS LARGER.
  
 4. SHEET A0 STATES THAT THIS IS A LEVEL 2 ALTERATION.
 IS THIS ALSO A CHANGE OF OCCUPANCY?
  
 5. THE PARKING LOT DOES NOT COMPLY WITH THE FLORIDA
 BUILDING CODE OR ADA. THE ACCESSIBLE PARKING SPACE IS
 NOT LOCATED ON THE CLOSEST ROUTE. SUBMIT A PERMIT
 APPLICATION TO BRING THE PARKING LOT INTO COMPLIANCE.
 IT APPEARS THAT THE PARKING LOT WAS RESTRIPED SOME TIME
 BETWEEN 2009 AND 2011 WITHOUT A PERMIT.
  
 6. PAPA RECORDS SHOW THREE SUITE NUMBERS FOR THIS
 LOCATION. DOES APPLICANT PREFER SEPARATE ADDRESSES?
 THIS MAY BE POSSIBLE, PLEASE ADVISE.
  
 THE APPLICATION IS FOR SUITE 102, BUT IF SUBWAY IS
 #101, SHOULDN'T THIS UNIT BE #103? PREVIOUS PERMITS
 SHOW THAT SUITE #102 IS IN THE CENTER; IT IS NOT CLEAR
 WHY THE APPLICATION IS FOR SUITE 102.
  
 7. PROVIDE TOTAL SQUARE FOOT AREA FOR THIS SPACE, FBC
 CHAPTER 10. LS1 SHOWS AN OCCUANT LOAD OF 4 FOR AN
 OFFICE, BUT NO OFFICE IS SHOWN ON THE PLAN. REVISE TO
 CLARIFY.
  
 8. REVISE PLAN TO PROVIDE INFORMATION ABOUT THE
 STOCKROOM AND THE STORAGE AREAS; WHAT WILL BE STORED IN
 THESE SPACES? FBC 107.
  
 9. A LOBBY IS SHOWN, BUT PLAN STATES THIS IS
 MERCANTILE. WHERE IS THE STORE? ONLY A LOBBY, SERVICES
 AREA, STOCKROOM AND STORAGE ARE SHOWN, FBC 107.
  
 10. REVISE PLAN TO CLARIFY WHAT THE PURPOSE IS OF THE
 "SERVICE AREA". IF THIS IS A CHECK OUT COUNTER, REVISE
 PLAN TO INCLUDE DETAILS TO SHOW COMPLIANCE WITH FBC A
 904, CHECK OUT AISLES AND SALES AND SERVICE COUNTERS.
  
 11. THE UNNUMBERED SWING DOOR LACKS THE MANEUVERING
 CLEARANCE REQUIRED BY FBC A 404.2.4, SEE FIGURE
 404.2.4.1(A).
  
 12. REVISE PLAN TO SHOW DETAILS FOR THE ENTRANCE TO
 SHOW COMPLIANCE WITH FBC A 303.
  
 13. PLAN INCLUDES A DESCRIPTIVE NOTE ON EACH SHEET THAT
 STATES "BUILDING REPAIRS"; WHAT WILL BE REPAIRED? FBC
 107.
  
  