| Notes |
| Date |
Text |
| 2018-03-12 11:06:29 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040807 | | | 3/12/18 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET M2.1.1: AS PREVIOUSLY NOTED IN THE 3RD REVIEW, | | | THE SHOP (FAB LAB) SHALL HAVE AN INDEPENDENT EXHAUST | | | SYSTEM AND SHALL NOT BE CONNECTED TO THE TOILET ROOM | | | EXHAUST DUCT. | | | | | | 2) M2.1.1: RECIRCULATION OF AIR FROM THE FAB LAB IS | | | LIMITED TO 10% PER FOOTNOTE G TABLE 403.3. THE PLAN | | | DOES NOT CLEARLY SHOW IF AIR IS BEING RETURNED VIA THE | | | 30X16" DUCT- PLEASE CLARIFY. | | | | | | 3) M2.2.1: FIRE DAMPERS ARE MISSING WHERE THE 28X16 AND | | | 22X12 DUCTS ARE PENETRATING THE FIRE-RATED SHAFT. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|