| Plan Review Notes For Permit 17040807 |
| Permit Number |
17040807 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2018-03-15 15:34:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. VALUE IS LOWER THAN ICC TABLES PER SF; PROVIDE | | | CONTRACT AND COST BREAKDOWN FOR REVIEW, OR AGREE FOR | | | VALUE TO BE ADJUSTED TO ICC TABLES. THIS MAY BE | | | ADDRESSED BY EMAIL. | | | | | | 2. PLEASE REMOVE THE STEEL BUILDING PAGES FROM THE | | | SUBMITTAL AS THEY WERE ALREADY APPROVED UNDER THE | | | FOUNDATION/STRUCTURE PERMIT. | | | | | | 3. SEE PREVIOUS LIST REGARDING ACCESSIBLE SIGHT LINE. | | | RESPONSE LETTER STATES THAT THIS IS ON THE "A" SHEETS, | | | BUT I WAS UNABLE TO LOCATE THIS INFORMATION. THIS | | | PERMIT WILL BE PASSED WITH PROVISO, COMPLIANCE | | | REQUIRED, TO BE VERIFIED AT INSPECTION, REVISION | | | REQUIRED SUBJECT TO FIELD INSPECTOR'S DISCRETION. | | | | | | |
|