| 2018-02-12 07:13:03 | 3RD REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: PREVIOUS COMMENTS NOT COMPLIED |
| | |
| | 3RD REQUEST 2. PLEASE PROVIDE A FIXTURE COUNT |
| | BREAKDOWN. PER WPB AMEND TO FBC 107.3.5.1.3 |
| | |
| | 2ND REQUEST 1.THE CIRCUIT VENT CONNECTION SHALL BE |
| | LOCATED BETWEEN THE TWO MOST UPSTREAM WATER CLOSET |
| | DRAINS. THE VENT SHALL CONNECT TO THE HORIZONTAL BRANCH |
| | AND SHALL BE INSTALLED IN ACCORDANCE WITH SECTION 905. |
| | THE CIRCUIT VENT PIPE SHALL NOT RECEIVE THE DISCHARGE |
| | OF ANY SOIL OR WASTE. PER FBC PL 914.2 |
| | |
| | 2ND REQUEST 4. CIVIL SHT. #7 OF 8 SHOWS A GAS MAIN |
| | RUNNING UNDER PROPOSED BUILDING GAS LINES SHALL NOT RUN |
| | UNDER BUILDING WILL NEED TO BE RELOCATED.PER FBC FG |
| | 404.14 |
| | |
| | 2ND REQUEST 5. THE CIVIL SHT #7 OF 8 THE CONFIGURATION |
| | OF GREASE INTERCEPTOR DOES NOT MATCH EXISTING |
| | INSTALLATION UNDER PERMIT 16041215. PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 2ND REQUEST 6. PROVIDE DETAILS FOR ACCESSIBILITY IN |
| | BATHROOMS, DRINKING FOUNTAIN AND CLASSROOM SINKS. PER |
| | FBC ACC CHAPTER 6 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | |