Plan Review Notes
Plan Review Notes For Permit 17040807
Permit Number 17040807
Review Stop M
Sequence Number 3
Notes
Date Text
2018-02-06 13:17:193RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION
 CODES
 PERMIT #17040807
 2/6/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE SUBMITTED ENERGYGAUGE COMPLIANCE FORM, AND THE
 AC LOAD CALCULATIONS INDICATE AC SYSTEMS EXCEEDING 15
 TONS WHICH REQUIRES THE ENGINEER OF RECORD TO PROVIDE
 HIS SIGNATURE AND SEAL ON THE DOCUMENTS- SECTION
 C103.1.1.1.2 FLORIDA ENERGY CONSERVATION CODE.
  
 2) THE AIRSOCK DUCKWORK SHALL BE CONSTRUCTED WITH CLASS
 0 OR CLASS 1 MATERIAL AND SHALL COMPLY WITH UL 181-
 SECTION 603.5. PLEASE PROVIDE A PRODUCT DATA SHEET WITH
 SHOP DRAWING APPROVAL STAMP BY THE EOR.
  
 3) ACCORDING TO THE RESPONSE NARRATIVE BY KAMM
 ENGINEERING THE FAB LAB IS ACTUALLY A METAL/WOOD SHOP.
 PLEASE SEE SECTIONS 510.2.1, 510.4, AND 511 AND PROVIDE
 AN INDEPENDENT EXHAUST SYSTEM FOR THE ROOM (NOT
 CONJLOINED WITH THE RESTROOM), AND A DUCT COLLECTION
 SYSTEM FOR THE SHOP EQUIPMENT.
  
 4) ACCORDING TO THE RESPONSE NARRATIVE BY KAMM
 ENGINEERING, THE WIND LOAD ENGINEERING IS BE PROVIDED
 BY OTHERS AS A DEFERRED SUBMITTAL:
  
 1) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
 2) DEFERRED SUBMITTAL. FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  