| 2018-02-06 13:17:19 | 3RD REVIEW FBC-2014 MECHANICAL, ENERGY CONSERVATION |
| | CODES |
| | PERMIT #17040807 |
| | 2/6/18 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE SUBMITTED ENERGYGAUGE COMPLIANCE FORM, AND THE |
| | AC LOAD CALCULATIONS INDICATE AC SYSTEMS EXCEEDING 15 |
| | TONS WHICH REQUIRES THE ENGINEER OF RECORD TO PROVIDE |
| | HIS SIGNATURE AND SEAL ON THE DOCUMENTS- SECTION |
| | C103.1.1.1.2 FLORIDA ENERGY CONSERVATION CODE. |
| | |
| | 2) THE AIRSOCK DUCKWORK SHALL BE CONSTRUCTED WITH CLASS |
| | 0 OR CLASS 1 MATERIAL AND SHALL COMPLY WITH UL 181- |
| | SECTION 603.5. PLEASE PROVIDE A PRODUCT DATA SHEET WITH |
| | SHOP DRAWING APPROVAL STAMP BY THE EOR. |
| | |
| | 3) ACCORDING TO THE RESPONSE NARRATIVE BY KAMM |
| | ENGINEERING THE FAB LAB IS ACTUALLY A METAL/WOOD SHOP. |
| | PLEASE SEE SECTIONS 510.2.1, 510.4, AND 511 AND PROVIDE |
| | AN INDEPENDENT EXHAUST SYSTEM FOR THE ROOM (NOT |
| | CONJLOINED WITH THE RESTROOM), AND A DUCT COLLECTION |
| | SYSTEM FOR THE SHOP EQUIPMENT. |
| | |
| | 4) ACCORDING TO THE RESPONSE NARRATIVE BY KAMM |
| | ENGINEERING, THE WIND LOAD ENGINEERING IS BE PROVIDED |
| | BY OTHERS AS A DEFERRED SUBMITTAL: |
| | |
| | 1) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. |
| | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| | NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT |
| | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| | THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| | OFFICIAL. |
| | 2) DEFERRED SUBMITTAL. FBC 107.3.4.1 PRODUCT APPROVALS. |
| | THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE |
| | 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |